• URD Cable Copper and Aluminum

    Applications
    ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.

    Description
    Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethyleneÌý(TRXLPE)Ìýjacket.

    Construction
    °ä´Ç²Ô»å³Ü³¦³Ù´Ç°ù:Ìý
    Class A or B compact concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
    Conductor Shield:Ìý Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
    Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
    Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
    Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
    Water-blocking agents:Ìý Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
    Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirementsÌýthe tables below,Ìýwhen tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant.Ìý The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.

    Designed for 40 years of service.

    Options
    • Copper Conductors
    • Black TRXLPE jacket with no stripes
    • Multiplex cables

    Physical Properties of Extruded-to-Fill XLPE Jacket
    Unaged Tensile Strength, min. (PSI) 1500
    Aged* Tensile Strength, min. ret. (%) 70
    Unaged Elongated, min. (%) 150
    Aged* Elongated, min. ret. (%)Ìý 70
    Heat Distortion 1 hr at 131 ºC, max. (%)Ìý 30
    * Aged for 168 hrs at 121 ºC


    Insulation Temperature Rating
    Normal 105º C
    Emergency* 140º C
    Short CircuitÌý-ÌýShield 350º C
    Short Circuit - Conductor 250º C
    *Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable

    Standards
    • ASTM B-231 (Compact) or ASTM B-400 (Compressed)
    • AEIC CS8
    • ICEA S-94-649
    • ICEA T-31-610
    • ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
    • UL 1072 MV-105
    • CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

    NOTES
    1. Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
    2. Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90ºC-cm/ W, earth ambient of 20ºC, neutral wires grounded at both ends, 75% and 100%Ìýload factor, conductor temperature of 105ºC, and 36" depth of burial.

    Ìý

  • URD Cable Copper and Aluminum

    Applications
    ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.

    Description
    Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethyleneÌý(TRXLPE)Ìýjacket.

    Construction
    °ä´Ç²Ô»å³Ü³¦³Ù´Ç°ù:Ìý
    Class A or B compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
    Conductor Shield:Ìý Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
    Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
    Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
    Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
    Water-blocking agents:Ìý Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
    Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirementsÌýthe tables below,Ìýwhen tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant.Ìý The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.

    Designed for 40 years of service.

    Options
    • Copper Conductors
    • Black TRXLPE jacket with no stripes
    • Multiplex cables

    Physical Properties of Extruded-to-Fill XLPE Jacket
    Unaged Tensile Strength, min. (PSI) 1500
    Aged* Tensile Strength, min. ret. (%) 70
    Unaged Elongated, min. (%) 150
    Aged* Elongated, min. ret. (%)Ìý 70
    Heat Distortion 1 hr at 131 ºC, max. (%)Ìý 30
    * Aged for 168 hrs at 121 ºC


    Insulation Temperature Rating
    Normal 105º C
    Emergency* 140º C
    Short CircuitÌý-ÌýShield 350º C
    Short Circuit - Conductor 250º C
    *Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable

    Standards
    • ASTM B-231 (Compact) or ASTM B-400 (Compressed)
    • AEIC CS8
    • ICEA S-94-649
    • ICEA T-31-610
    • ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
    • UL 1072 MV-105
    • CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

    NOTES
    1. Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
    2. Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90ºC-cm/ W, earth ambient of 20ºC, neutral wires grounded at both ends, 75% and 100%Ìýload factor, conductor temperature of 105ºC, and 36" depth of burial.

    Ìý

  • URD Cable Copper and Aluminum

    Applications
    ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.

    Description
    Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethyleneÌý(TRXLPE)Ìýjacket.

    Construction
    °ä´Ç²Ô»å³Ü³¦³Ù´Ç°ù:Ìý
    Class A or B concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
    Conductor Shield:Ìý Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
    Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
    Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
    Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
    Water-blocking agents:Ìý Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
    Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirementsÌýthe tables below,Ìýwhen tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant.Ìý The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.

    Designed for 40 years of service.

    Options
    • Copper Conductors
    • Black TRXLPE jacket with no stripes
    • Multiplex cables

    Physical Properties of Extruded-to-Fill XLPE Jacket
    Unaged Tensile Strength, min. (PSI) 1500
    Aged* Tensile Strength, min. ret. (%) 70
    Unaged Elongated, min. (%) 150
    Aged* Elongated, min. ret. (%)Ìý 70
    Heat Distortion 1 hr at 131 ºC, max. (%)Ìý 30
    * Aged for 168 hrs at 121 ºC


    Insulation Temperature Rating
    Normal 105º C
    Emergency* 140º C
    Short CircuitÌý-ÌýShield 250º C
    Short Circuit - Conductor 350º C
    *Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable

    Standards
    • ASTM B-231 (Compact) or ASTM B-400 (Compressed)
    • AEIC CS8
    • ICEA S-94-649
    • ICEA T-31-610
    • ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
    • UL 1072 MV-105
    • CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

    NOTES
    1. Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
    2. Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90ºC-cm/ W, earth ambient of 20ºC, neutral wires grounded at both ends, 75% and 100%Ìýload factor, conductor temperature of 105ºC, and 36" depth of burial.

    Ìý

  • URD Cable Copper and Aluminum

    Applications
    ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.

    Description
    Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength ±Ê´Ç·É±ð°ù³Ò³Ü²¹°ù»å® TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethyleneÌý(TRXLPE)Ìýjacket.

    Construction
    °ä´Ç²Ô»å³Ü³¦³Ù´Ç°ù:Ìý
    Class A or B concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
    Conductor Shield:Ìý Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
    Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
    Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
    Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
    Water-blocking agents:Ìý Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
    Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirementsÌýthe tables below,Ìýwhen tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant.Ìý The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.

    Designed for 40 years of service.

    Options
    • Copper Conductors
    • Black TRXLPE jacket with no stripes
    • Multiplex cables

    Physical Properties of Extruded-to-Fill XLPE Jacket
    Unaged Tensile Strength, min. (PSI) 1500
    Aged* Tensile Strength, min. ret. (%) 70
    Unaged Elongated, min. (%) 150
    Aged* Elongated, min. ret. (%)Ìý 70
    Heat Distortion 1 hr at 131 ºC, max. (%)Ìý 30
    * Aged for 168 hrs at 121 ºC


    Insulation Temperature Rating
    Normal 105º C
    Emergency* 140º C
    Short CircuitÌý-ÌýShield 250º C
    Short Circuit - Conductor 350º C
    *Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable

    Standards
    • ASTM B-231 (Compact) or ASTM B-400 (Compressed)
    • AEIC CS8
    • ICEA S-94-649
    • ICEA T-31-610
    • ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
    • UL 1072 MV-105
    • CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

    NOTES
    1. Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
    2. Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90ºC-cm/ W, earth ambient of 20ºC, neutral wires grounded at both ends, 75% and 100%Ìýload factor, conductor temperature of 105ºC, and 36" depth of burial.