Powerguard® Medium Voltage Cable in Duct

Duct Materials

The duct shall be extruded from either medium density polyethylene type II, class C, category 5, or high density polyethylene type III, class C, category 5 as outlined in ASTM D1248.

Duct Dimensions
The following duct dimensions are recommended, however, 7mÊÓƵ will provide duct to customer's required dimensions when specified.

Contact us for compatible cable constructions.


The cable shown in the illustration is 



UPDATED 02/14/2024

Unit of Measure
Items
Cable in Duct

Powerguard Medium Voltage Cable in Duct

Cable in Duct

Powerguard Medium Voltage Cable in Duct

Cable in Duct

Powerguard Medium Voltage Cable in Duct
Conduit
Size
N/A 1 1/4 Inches N/A 1 1/2 Inches N/A 2 Inches
Conduit
Outer
Diameter
N/A 1.66 Inches N/A 1.90 Inches N/A 2.38 Inches
Minimum
Wall
Thickness
N/A 100 mls N/A 115 mls N/A 145 mls
Bending
Radius
N/A 18 Inches N/A 21 Inches N/A 26 Inches
Max.
Cable
Diameter
N/A 1.05 Inches N/A 1.20 Inches N/A 1.5 Inches
Typical
Unjacketed
Cond. Size
N/A #2 through 2/0 N/A 1/0 through 250 N/A 4/0 through 500
Elongation N/A 400 %
Melt
Index
Max.
N/A .4
Brittleness
Temp.
ºC max.
Medium
N/A -45 ºC
Brittleness
Temp.
ºC max.
High
N/A -75 ºC