For information on conductor sizes or voltage ratings not shown in the tables, contact your 7mÊÓƵ sales representative.
Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.
Items |
A2-01MV15GT10501 PowerGuard® 15kV 100% Shielded Power Cable AL Conductor 175 mils TRXLPE Copper Tape PVC Jacket |
A1-01MV15GT10501 PowerGuard® 15kV 100% Shielded Power Cable AL Conductor 175 mils TRXLPE Copper Tape PVC Jacket |
A1/0-01MV15GT10501 PowerGuard® 15kV 100% Shielded Power Cable AL Conductor 175 mils TRXLPE Copper Tape PVC Jacket |
A2/0-01MV15GT10501 PowerGuard® 15kV 100% Shielded Power Cable AL Conductor 175 mils TRXLPE Copper Tape PVC Jacket |
A3/0-01MV15GT10501 PowerGuard® 15kV 100% Shielded Power Cable AL Conductor 175 mils TRXLPE Copper Tape PVC Jacket |
|||||
Compressed Conductor Aluminum Size/ # of Wires |
N/A 2 / 7 | N/A 1 / 19 | N/A 1/0 / 19 | N/A 2/0 / 19 | N/A 3/0 / 19 | |||||
Nominal Insulation Thickness (mil) |
N/A 175 | |||||||||
Diameter Insulation MIN. (in.)1 |
N/A 0.635 | N/A 0.675 | N/A 0.715 | N/A 0.76 | N/A 0.81 | |||||
Diameter Insulation MAX. (in.)1 |
N/A 0.72 | N/A 0.76 | N/A 0.8 | N/A 0.845 | N/A 0.895 | |||||
Diameter 5 mil CU Tape (in.)1 |
N/A 0.741 | N/A 0.78 | N/A 0.82 | N/A 0.864 | N/A 0.914 | |||||
Diameter PVC Jacket (in.)1 |
N/A 0.87 | N/A 0.939 | N/A 0.979 | N/A 1.023 | N/A 1.073 | |||||
Nominal Jacket Thickness (in.)1 |
N/A 0.08 | |||||||||
Approximate Weight AL Conductor (lbs/MFT)1 |
N/A 62 | N/A 78 | N/A 99 | N/A 125 | N/A 158 | |||||
Approximate Weight CU Shield (lbs/MFT)1 |
N/A 52 | N/A 55 | N/A 58 | N/A 61 | N/A 65 | |||||
Approximate Weight Total Conductor (lbs/MFT)1 |
N/A 364 | N/A 422 | N/A 463 | N/A 513 | N/A 572 | |||||
Ampacity2 Direct Buried |
N/A 165 | N/A 190 | N/A 215 | N/A 245 | N/A 280 | |||||
Ampacity2 In Duct |
N/A 125 | N/A 145 | N/A 165 | N/A 185 | N/A 210 | |||||
|