Quadruplex Conductor Type URD Cable - Aluminum Conductor
0-v-secondary-type-urd-cable-br-aluminum-conductor
-
Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor
Applications
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.
Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
- B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
- B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
- Secondary UD quadruplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- "USE-2" per UL 854 available upon request
- Cable in Duct (CIC)
- Abrasion Resistant
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition. -
Quadruplex Conductor 600V Secondary Type URD Cable (8000) RHH/RHW-2 USE-2 - Aluminum Conductor
Applications
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed (8176-H24) aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.
Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.- B-800 8000 Series Aluminum Alloy Wire for Electrical Purposes
- B-801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation.
- B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
- Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- UL Standard 44 for Type RHH or RHW-2
- UL standard 854 for Type USE-2.
- Cable in Duct (CIC)
- Abrasion Resistant
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition. -
PACKAGING INFORMATION: Quadruplex Conductor 600V Secondary Type URD Cable
Packaging Information: Quadruplex Conductor 600V Secondary Type URD Cable CODE
WORDALUMINUM
CONDUCTORSSTANDARD PACKAGE SIZES CONDUCTOR
SIZE AND
STRANDINGNEUTRAL
SIZE AND
STRANDINGLENGTH WEIGHT
XLP
(lbs)REEL
SIZETulsa 4-7 4-7 1,000 258 NRC 32.24 1,500 387 NRC 34.26 Dyke 2-7 4-7 1,000 346 NRC 32.24 1,400 484 NRC 40.24 1,500 519 NRC 40.24 Wittenberg 2-7 2-7 1,000 375 NRC 32.24 1,400 525 NRC 40.24 1,500 563 NRC 40.24 Notre Dame 1/0-19 2-7 1,000 541 NRC 40.24 1,400 757 NRC 48.28 1,500 812 NRC 48.28 Purdue 1/0-19 1/0-19 1,000 596 NRC 42.26 1,400 834 NRC 48.28 1,500 894 NRC 48.28 Syracuse 2/0-19 1-19 1,000 664 NRC 42.26 1,400 930 NRC 50.32 1,500 996 NRC 50.32 Lafayette 2/0-19 2/0-19 1,000 720 NRC 42.28 Wake Forest 4/0-19 2/0-19 1,000 979 NRC 50.32 1,400 1371 NRC 54.32 1,500 1469 NRC 54.32 Earlham 4/0-19 4/0-19 1,000 1066 NRC 50.32 1,500 1599 NRC 54.32 Slippery Rock 350-37 4/0-19 1,000 1544 NRC 60.28 1,400 2162 NRC 66.28