Triplex Conductor Type URD Cable - Aluminum Conductor
triplex-conductor-urd-cable-aluminum-conductor
-
Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
Construction
Conductors are stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
- B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
- B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
- Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- "USE-2" per UL 854 available upon request.
- Cable in Duct (CIC)
- Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductors triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition. -
Triplex Conductor 600V Secondary Type URD Cable - (8000) RHH/RHW-2 USE-2 - Aluminum Conductor
Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
Construction
Concentric stranded or compressed 8000 (8176-H24) aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.- B-800 8000 Series Aluminum Alloy Wire for Electrical Purposes
- B-801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation.
- B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
- Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- UL Standard 44 for Type RHH or RHW-2
- UL standard 854 for Type USE-2.
- Cable in Duct (CIC)
- Abrasion Resistant
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition. -
PACKAGING INFORMATION: Triplex Conductor 600V Secondary Type URD Cable
Packaging Information: Triplex Conductor 600V Secondary Type URD Cable CODE
WORDALUMINUM
CONDUCTORSSTANDARD PACKAGE SIZES CONDUCTOR
SIZE AND
STRANDINGNEUTRAL
SIZE AND
STRANDINGLENGTH WEIGHT
XLP
(lbs)REEL
SIZEStephens 7-2 4-7 1,000 262 NRC 32.24 Ramapo 7-2 2-7 1,000 291 NRC 32.24 Brenau 1/0-19 2-7 1,000 409 NRC 36.24 Bergen 1/0-19 1/0-19 1,000 465 NRC 40.24 Converse 2/0-19 1-19 1,000 504 NRC 40.24 Hunter 2/0-19 2/0-19 1,000 561 NRC 40.24 Hollins 3/0-19 1/0-19 1,000 609 NRC 42.26 Rockland 3/0-19 3/0-19 1,000 680 NRC 42.26 Sweetbriar 4/0-19 2/0-19 1,000 740 NRC 42.26 Monmouth 4/0-19 4/0-19 1,000 827 NRC 45.28 Pratt 250-37 3/0-19 1,000 896 NRC 50.32 Wesleyan 350-37 4/0-19 1,000 1,168 NRC 50.32 Rider 500-37 350-37 1,000 1,606 NRC 58.32