PowerGuard® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.
Description
Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength PowerGuard® TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethylene (TRXLPE) jacket.
Construction
Conductor: Class A or B concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
Water-blocking agents: Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirements the tables below, when tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant. The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.
Designed for 40 years of service.
- Copper Conductors
- Black TRXLPE jacket with no stripes
- Multiplex cables
Physical Properties of Extruded-to-Fill XLPE Jacket
|
|
Unaged Tensile Strength, min. (PSI) | 1500 |
Aged* Tensile Strength, min. ret. (%) | 70 |
Unaged Elongated, min. (%) | 150 |
Aged* Elongated, min. ret. (%) | 70 |
Heat Distortion 1 hr at 131 ºC, max. (%) | 30 |
Insulation Temperature Rating | |
Normal | 105º C |
Emergency* | 140º C |
Short Circuit - Shield | 250º C |
Short Circuit - Conductor | 350º C |
Standards
- ASTM B-231 (Compact) or ASTM B-400 (Compressed)
- AEIC CS8
- ICEA S-94-649
- ICEA T-31-610
- ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
- UL 1072 MV-105
- CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution
NOTES
- Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
- Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90ºC-cm/ W, earth ambient of 20ºC, neutral wires grounded at both ends, 75% and 100% load factor, conductor temperature of 105ºC, and 36" depth of burial.
Items |
/Asset/URD-Cable-Aluminum.png A1/0-01UD35GT101X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - ELECTRICAL PROPERTIES |
/Asset/URD-Cable-Aluminum.png A1/0-01UD35GT203X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - ELECTRICAL PROPERTIES |
/Asset/URD-Cable-Aluminum.png A1/0-01UD35GT102X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - ELECTRICAL PROPERTIES |
/Asset/URD-Cable-Aluminum.png A1/0-01UD35GT103X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - ELECTRICAL PROPERTIES |
/Asset/URD-Cable-Aluminum.png A2/0-01UD35GT101X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - ELECTRICAL PROPERTIES |
|||||
Conductor AL Size 7mÊÓƵ or kcmil |
N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 2/0 | |||||
Neutral Size |
N/A Full | N/A 2/3 | N/A 1/2 | N/A 1/3 | N/A Full | |||||
TREFOIL ________ Pos/Neg Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 249.56+52.86J | N/A 249.14+52.55J | N/A 248.92+52.57J | N/A 248.7+52.58J | N/A 193.37+50.44J | |||||
TREFOIL ________ Zero Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 476.61+117.13J | N/A 543.03+189.05J | N/A 579.89+258.39J | N/A 604.84+371.43J | N/A 386.24+89.94J | |||||
TREFOIL ________ Ampacity LF=100% |
N/A 203 | N/A 203 | N/A 203 | N/A 203 | N/A 235 | |||||
TREFOIL ________ Ampacity LF=75% |
N/A 232 | N/A 232 | N/A 232 | N/A 232 | N/A 269 | |||||
FLAT SPACED @7.5 INCHES ________ Pos/Neg Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 261.25+92.78J | N/A 256.92+94.75J | N/A 254.59+95.48J | N/A 252.18+96.04J | N/A 207.6+88.54J | |||||
FLAT SPACED @7.5 INCHES ________ Zero Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 463.04+121.02J | N/A 519.17+191.9J | N/A 546.98+257.04J | N/A 560.1+357.66J | N/A 376.82+93.45J | |||||
FLAT SPACED @7.5 INCHES ________ Ampacity LF=100% |
N/A 223 | N/A 224 | N/A 225 | N/A 226 | N/A 275 | |||||
FLAT SPACED @7.5 INCHES ________ Ampacity LF=75% |
N/A 250 | N/A 251 | N/A 252 | N/A 253 | N/A 289 | |||||
FLAT SPACED TOUCHING ________ Pos/Neg Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 249.31+57.34J | N/A 248.6+58.15J | N/A 248.16+58.22J | N/A 247.72+58.27J | N/A 193.89+55.69J | |||||
FLAT SPACED TOUCHING ________ Zero Seq Impedance (µΩ/´Ú±ð±ð³Ù) |
N/A 473.3+116.99J | N/A 538.21+188.58J | N/A 574.08+257.24J | N/A 597.79+368.65J | N/A 383.53+89.97J | |||||
FLAT SPACED TOUCHING ________ Ampacity LF=100% |
N/A 204 | N/A 204 | N/A 204 | N/A 204 | N/A 235 | |||||
FLAT SPACED TOUCHING ________ Ampacity LF=75% |
N/A 233 | N/A 233 | N/A 233 | N/A 233 | N/A 270 | |||||
|