Applications
For use in closed environments or populated spaces such as auditoriums, arenas and health facilities where more stringent customer specifications for smoke and halogen-free materials are desired. Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is a major concern, where maximum performance will be demanded and where space is limited. For use in free air, raceways or direct burial in accordance with NEC
Construction
Conductor: 14 7mÊÓƵ thru 1000 kcmil compressed tinned copper per ASTM B33, Class B stranding per ASTM B8
Insulation: Composite Low-Smoke, Zero-Halogen Cross-linked Polyolefin (LSZH XLPO) colored for contrast with black Low-Smoke, Zero-Halogen Cross-linked Polyolefin (LSZH XLPO)
Print: AMERICAN WIRE GROUP LSZH TYPE USE-2 OR RHH OR RHW-2 (SIZE) 600 V OIL RES I SUN RES -40C ST1* FOR CT USE* (UL) DAY/MONTH/YEAR OF MFG SEQUENTIALFOOTAGE MARK * “ST1” and “FOR CT USE” on 1/0 7mÊÓƵ and larger.
Features
- Rated at 90°C wet or dry
- Low-Smoke, Zero-Halogen insulation systemExtra-tough, mechanically rugged composite insulation construction
- Low Friction for easy pulling on 8 7mÊÓƵ and larger
- Excellent electrical, thermal and physical properties
- Excellent moisture resistance, exceeding UL 44 requirements
- Excellent resistance to crush, compression cuts and heat deformation
- Excellent flame resistance
- Resistant to most oils and chemicals
- UV/sunlight-resistant
- Rated ST-1 for Limited Smoke per UL 44 on sizes 1/0 7mÊÓƵ and larger
- Stable electrical properties over a broad temperature range
- Excellent low temperature cold bend characteristics, meets cold bend and cold impact test at -40°C
Compliances:
- National Electrical Code (NEC)
- “FOR CT USE” on 1/0 7mÊÓƵ and larger in accordance with NEC
- UL 44 Type RHH/RHW-2
- UL 854 Type USE-2
- Limited Smoke rating per UL 44 and UL 1685
- Compressed tinned copper per ASTM B33
- Class B stranding per ASTM B8
- ICEA T-33-655 smoke, halogen and acid gas requirements
- ICEA S-95-658/NEMA WC70
Flame Test Compliances:
- For 1/0 7mÊÓƵ and larger: IEEE 383, IEEE 1202/CSA FT4
- UL 1685
Other Compliances:
- EPA 40 CFR, Part 261 for leachable lead content per TCLP
- OSHA Acceptable
- RoHS Compliant
Packaging: Material cut to length and shipped on non-returnable wood reels
Options:
- 2 kV version
- Bare copper conductor
- Other stranding available
Item # |
Size
|
Insulation
|
Nominal
|
Minimum
|
Minimum
|
Minimum
|
Minimum
|
Copper
|
Net
|
---|---|---|---|---|---|---|---|---|---|
14-01XLSOH 14-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 14 |
Insulation Thickness (mil) N/A 7/.0242 |
Nominal Conductor Diameter (in) N/A 0.07 |
Minimum Average Insulation Thickness (in) N/A 0.030 |
Minimum Average Insulation Diameter (in) N/A 0.14 |
Minimum Average Jackness Thickness (in) N/A 0.015 |
Minimum Average Jackness Diameter (in) N/A 0.17 |
Copper Weight (lb/MFT) N/A 13 |
Net Weight (lb/MFT) N/A 24 |
12-01XLSOH 12-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 12 |
Insulation Thickness (mil) N/A 7/.0305 |
Nominal Conductor Diameter (in) N/A 0.09 |
Minimum Average Insulation Thickness (in) N/A 0.030 |
Minimum Average Insulation Diameter (in) N/A 0.16 |
Minimum Average Jackness Thickness (in) N/A 0.015 |
Minimum Average Jackness Diameter (in) N/A 0.19 |
Copper Weight (lb/MFT) N/A 20 |
Net Weight (lb/MFT) N/A 33 |
10-01XLSOH 10-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 10 |
Insulation Thickness (mil) N/A 7/.0385 |
Nominal Conductor Diameter (in) N/A 0.12 |
Minimum Average Insulation Thickness (in) N/A 0.030 |
Minimum Average Insulation Diameter (in) N/A 0.18 |
Minimum Average Jackness Thickness (in) N/A 0.015 |
Minimum Average Jackness Diameter (in) N/A 0.21 |
Copper Weight (lb/MFT) N/A 32 |
Net Weight (lb/MFT) N/A 48 |
8-01XLSOH 8-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 8 |
Insulation Thickness (mil) N/A 7/.0486 |
Nominal Conductor Diameter (in) N/A 0.15 |
Minimum Average Insulation Thickness (in) N/A 0.045 |
Minimum Average Insulation Diameter (in) N/A 0.24 |
Minimum Average Jackness Thickness (in) N/A 0.015 |
Minimum Average Jackness Diameter (in) N/A 0.28 |
Copper Weight (lb/MFT) N/A 50 |
Net Weight (lb/MFT) N/A 77 |
6-01XLSOH 6-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 6 |
Insulation Thickness (mil) N/A 7/.0612 |
Nominal Conductor Diameter (in) N/A 0.18 |
Minimum Average Insulation Thickness (in) N/A 0.045 |
Minimum Average Insulation Diameter (in) N/A 0.28 |
Minimum Average Jackness Thickness (in) N/A 0.030 |
Minimum Average Jackness Diameter (in) N/A 0.35 |
Copper Weight (lb/MFT) N/A 81 |
Net Weight (lb/MFT) N/A 122 |
4-01XLSOH 4-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 4 |
Insulation Thickness (mil) N/A 7/.0772 |
Nominal Conductor Diameter (in) N/A 0.23 |
Minimum Average Insulation Thickness (in) N/A 0.045 |
Minimum Average Insulation Diameter (in) N/A 0.33 |
Minimum Average Jackness Thickness (in) N/A 0.030 |
Minimum Average Jackness Diameter (in) N/A 0.39 |
Copper Weight (lb/MFT) N/A 129 |
Net Weight (lb/MFT) N/A 178 |
2-01XLSOH 2-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 2 |
Insulation Thickness (mil) N/A 7/.0974 |
Nominal Conductor Diameter (in) N/A 0.29 |
Minimum Average Insulation Thickness (in) N/A 0.045 |
Minimum Average Insulation Diameter (in) N/A 0.39 |
Minimum Average Jackness Thickness (in) N/A 0.030 |
Minimum Average Jackness Diameter (in) N/A 0.46 |
Copper Weight (lb/MFT) N/A 205 |
Net Weight (lb/MFT) N/A 265 |
1/0-01XLSOH 1/0-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 1/0 |
Insulation Thickness (mil) N/A 19/.0740 |
Nominal Conductor Diameter (in) N/A 0.37 |
Minimum Average Insulation Thickness (in) N/A 0.055 |
Minimum Average Insulation Diameter (in) N/A 0.48 |
Minimum Average Jackness Thickness (in) N/A 0.045 |
Minimum Average Jackness Diameter (in) N/A 0.58 |
Copper Weight (lb/MFT) N/A 326 |
Net Weight (lb/MFT) N/A 422 |
2/0-01XLSOH 2/0-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 2/0 |
Insulation Thickness (mil) N/A 19/.0837 |
Nominal Conductor Diameter (in) N/A 0.41 |
Minimum Average Insulation Thickness (in) N/A 0.055 |
Minimum Average Insulation Diameter (in) N/A 0.53 |
Minimum Average Jackness Thickness (in) N/A 0.045 |
Minimum Average Jackness Diameter (in) N/A 0.63 |
Copper Weight (lb/MFT) N/A 411 |
Net Weight (lb/MFT) N/A 518 |
4/0-01XLSOH 4/0-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 4/0 |
Insulation Thickness (mil) N/A 19/.1055 |
Nominal Conductor Diameter (in) N/A 0.52 |
Minimum Average Insulation Thickness (in) N/A 0.055 |
Minimum Average Insulation Diameter (in) N/A 0.64 |
Minimum Average Jackness Thickness (in) N/A 0.045 |
Minimum Average Jackness Diameter (in) N/A 0.74 |
Copper Weight (lb/MFT) N/A 653 |
Net Weight (lb/MFT) N/A 785 |
250-01XLSOH 250-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 250 |
Insulation Thickness (mil) N/A 37/.0822 |
Nominal Conductor Diameter (in) N/A 0.56 |
Minimum Average Insulation Thickness (in) N/A 0.065 |
Minimum Average Insulation Diameter (in) N/A 0.70 |
Minimum Average Jackness Thickness (in) N/A 0.065 |
Minimum Average Jackness Diameter (in) N/A 0.85 |
Copper Weight (lb/MFT) N/A 772 |
Net Weight (lb/MFT) N/A 960 |
350-01XLSOH 350-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 350 |
Insulation Thickness (mil) N/A 37/.0973 |
Nominal Conductor Diameter (in) N/A 0.67 |
Minimum Average Insulation Thickness (in) N/A 0.065 |
Minimum Average Insulation Diameter (in) N/A 0.81 |
Minimum Average Jackness Thickness (in) N/A 0.065 |
Minimum Average Jackness Diameter (in) N/A 0.96 |
Copper Weight (lb/MFT) N/A 1081 |
Net Weight (lb/MFT) N/A 1299 |
500-01XLSOH 500-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 500 |
Insulation Thickness (mil) N/A 37/.1162 |
Nominal Conductor Diameter (in) N/A 0.80 |
Minimum Average Insulation Thickness (in) N/A 0.065 |
Minimum Average Insulation Diameter (in) N/A 0.94 |
Minimum Average Jackness Thickness (in) N/A 0.065 |
Minimum Average Jackness Diameter (in) N/A 1.09 |
Copper Weight (lb/MFT) N/A 1542 |
Net Weight (lb/MFT) N/A 1803 |
750-01XLSOH 750-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 750 |
Insulation Thickness (mil) N/A 61/.1109 |
Nominal Conductor Diameter (in) N/A 0.97 |
Minimum Average Insulation Thickness (in) N/A 0.080 |
Minimum Average Insulation Diameter (in) N/A 1.15 |
Minimum Average Jackness Thickness (in) N/A 0.065 |
Minimum Average Jackness Diameter (in) N/A 1.31 |
Copper Weight (lb/MFT) N/A 2316 |
Net Weight (lb/MFT) N/A 2664 |
1000-01XLSOH 1000-01XLSOH/Asset/lzsh-image.png |
Size 7mÊÓƵ or KCMIL N/A 1000 |
Insulation Thickness (mil) N/A 61/.1280 |
Nominal Conductor Diameter (in) N/A 1.13 |
Minimum Average Insulation Thickness (in) N/A 0.080 |
Minimum Average Insulation Diameter (in) N/A 1.31 |
Minimum Average Jackness Thickness (in) N/A 0.065 |
Minimum Average Jackness Diameter (in) N/A 1.46 |
Copper Weight (lb/MFT) N/A 3806 |
Net Weight (lb/MFT) N/A 3989 |