Applications
Type MC Cable is primarily used for services, feeders, and branch circuits as specified in the 2011 National Electric Code. Type MC cable with Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Used for power and lighting indoors, exposed or concealed, in cable tray where identified for such use; in a raceway, or in dry locations and embedded in plaster or against other masonry. Voltage rating for XHHW-2 conductors is 600V.
Construction
Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable. XLPE insulated XHHW-2 conductors are twisted with a bare conductor. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Rated 90°C wet or dry and is flame and sunlight resistant.
Specifications
Type MC cable with Type XHHW-2 conductors are manufactured and tested in accordance with the latest revisions of:
- UL 44 for Thermoset-Insulated Wires and Cables
- UL 83 for Thermoplastic-Insulated Wires and Cables
- UL 1479 Standard for Fire Tests of Through-Penetration Firestops.
- UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
- UL 1569 for Metal-Clad Cables.
- IEEE 1202 - Flame Testing of Cables for Use in Cable Tray, in Industrial and Commercial Occupancies (70,000 BTU/hr).
- ICEA T-29-520 - Vertical Cable Tray Flame Tests (210,000 Btu/hr).
- ICEA S-66-524 and requirements of the National Electric Code
- ICEA S-95-658 (NEMA WC 70) construction requirements
- Federal Specification J-C-30B
Color Code
Three Phase Conductors (3): Black, red, white
Ground Conductor (1): Bare
Other colors and stripes available by special order.
For Special Order
- The entire assembly can be covered with a PVC or CPE outer jacket (black or color). Jacketed MC Cable may be used in wet locations, either direct burial, in underground conduit, or overhead.
- Halogen free jackets are available upon request
- A black jacket (on individual conductors) with color stripes can be requested.
- Bare Ground conductor available upon request.
- For sizes not listed above please contact sales.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Size
|
Phase
|
Number
|
Diameter
|
Thickness
|
Size
|
Diameter
|
Thickness
|
Cabling
|
Overall
|
AL
|
Cable
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
A12-03MC12 A12-03MC12/Asset/MC 3C.png |
Size of Cable N/A 12-12-12+12 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 12 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 91 |
Thickness of Conductor Insulation (mils) N/A 30 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 12 |
Diameter of Ground (mils) N/A 91 |
Thickness of Ground Insulation (mils) N/A 30 |
Cabling Diameter (mils) N/A 366 |
Overall Diameter of Cable Over Armour (mils) N/A 640 |
AL Weight (lb/mft) N/A 93 |
Cable Weight (lb/mft) N/A 119 |
A10-03MC10 A10-03MC10/Asset/MC 3C.png |
Size of Cable N/A 10-10-10+10 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 10 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 116 |
Thickness of Conductor Insulation (mils) N/A 30 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 10 |
Diameter of Ground (mils) N/A 116 |
Thickness of Ground Insulation (mils) N/A 30 |
Cabling Diameter (mils) N/A 425 |
Overall Diameter of Cable Over Armour (mils) N/A 699 |
AL Weight (lb/mft) N/A 116 |
Cable Weight (lb/mft) N/A 147 |
A8-03MC10 A8-03MC10/Asset/MC 3C.png |
Size of Cable N/A 8-8-8+10 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 8 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 134 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 10 |
Diameter of Ground (mils) N/A 116 |
Thickness of Ground Insulation (mils) N/A 30 |
Cabling Diameter (mils) N/A 528 |
Overall Diameter of Cable Over Armour (mils) N/A 801 |
AL Weight (lb/mft) N/A 149 |
Cable Weight (lb/mft) N/A 198 |
A8-03MC8 A8-03MC8/Asset/MC 3C.png |
Size of Cable N/A 8-8-8+8 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 8 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 134 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 8 |
Diameter of Ground (mils) N/A 134 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 543 |
Overall Diameter of Cable Over Armour (mils) N/A 817 |
AL Weight (lb/mft) N/A 157 |
Cable Weight (lb/mft) N/A 212 |
A6-03MC8 A6-03MC8/Asset/MC 3C.png |
Size of Cable N/A 6-6-6+8 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 6 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 169 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 8 |
Diameter of Ground (mils) N/A 134 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 618 |
Overall Diameter of Cable Over Armour (mils) N/A 892 |
AL Weight (lb/mft) N/A 196 |
Cable Weight (lb/mft) N/A 258 |
A6-03MC6 A6-03MC6/Asset/MC 3C.png |
Size of Cable N/A 6-6-6+6 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 6 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 169 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 626 |
Overall Diameter of Cable Over Armour (mils) N/A 900 |
AL Weight (lb/mft) N/A 206 |
Cable Weight (lb/mft) N/A 271 |
A4-03MC6 A4-03MC6/Asset/MC 3C.png |
Size of Cable N/A 4-4-4+6 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 213 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 720 |
Overall Diameter of Cable Over Armour (mils) N/A 994 |
AL Weight (lb/mft) N/A 264 |
Cable Weight (lb/mft) N/A 339 |
A4-03MC4 A4-03MC4/Asset/MC 3C.png |
Size of Cable N/A 4-4-4+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 213 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 732 |
Overall Diameter of Cable Over Armour (mils) N/A 1006 |
AL Weight (lb/mft) N/A 280 |
Cable Weight (lb/mft) N/A 358 |
A3-03MC6 A3-03MC6/Asset/MC 3C.png |
Size of Cable N/A 3-3-3+6 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 238 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 772 |
Overall Diameter of Cable Over Armour (mils) N/A 1045 |
AL Weight (lb/mft) N/A 302 |
Cable Weight (lb/mft) N/A 382 |
A3-03MC4 A3-03MC4/Asset/MC 3C.png |
Size of Cable N/A 3-3-3+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 238 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 795 |
Overall Diameter of Cable Over Armour (mils) N/A 1069 |
AL Weight (lb/mft) N/A 320 |
Cable Weight (lb/mft) N/A 404 |
A3-03MC3 A3-03MC3/Asset/MC 3C.png |
Size of Cable N/A 3-3-3+3 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 238 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3 |
Diameter of Ground (mils) N/A 238 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 795 |
Overall Diameter of Cable Over Armour (mils) N/A 1069 |
AL Weight (lb/mft) N/A 330 |
Cable Weight (lb/mft) N/A 415 |
A2-03MC6 A2-03MC6/Asset/MC 3C.png |
Size of Cable N/A 2-2-2+6 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 268 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 843 |
Overall Diameter of Cable Over Armour (mils) N/A 1116 |
AL Weight (lb/mft) N/A 350 |
Cable Weight (lb/mft) N/A 438 |
A2-03MC4 A2-03MC4/Asset/MC 3C.png |
Size of Cable N/A 2-2-2+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 268 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 850 |
Overall Diameter of Cable Over Armour (mils) N/A 1124 |
AL Weight (lb/mft) N/A 366 |
Cable Weight (lb/mft) N/A 456 |
A2-03MC2 A2-03MC2/Asset/MC 3C.png |
Size of Cable N/A 2-2-2+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 268 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 866 |
Overall Diameter of Cable Over Armour (mils) N/A 1140 |
AL Weight (lb/mft) N/A 391 |
Cable Weight (lb/mft) N/A 485 |
A1-03MC4 A1-03MC4/Asset/MC 3C.png |
Size of Cable N/A 1-1-1+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 961 |
Overall Diameter of Cable Over Armour (mils) N/A 1234 |
AL Weight (lb/mft) N/A 431 |
Cable Weight (lb/mft) N/A 548 |
A1-03MC3 A1-03MC3/Asset/MC 3C.png |
Size of Cable N/A 1-1-1+3 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3 |
Diameter of Ground (mils) N/A 238 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 972 |
Overall Diameter of Cable Over Armour (mils) N/A 1246 |
AL Weight (lb/mft) N/A 443 |
Cable Weight (lb/mft) N/A 562 |
A1-03MC2 A1-03MC2/Asset/MC 3C.png |
Size of Cable N/A 1-1-1+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 972 |
Overall Diameter of Cable Over Armour (mils) N/A 1246 |
AL Weight (lb/mft) N/A 456 |
Cable Weight (lb/mft) N/A 576 |
A1-03MC1 A1-03MC1/Asset/MC 3C.png |
Size of Cable N/A 1-1-1+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 988 |
Overall Diameter of Cable Over Armour (mils) N/A 1262 |
AL Weight (lb/mft) N/A 474 |
Cable Weight (lb/mft) N/A 603 |
A1/0-03MC4 A1/0-03MC4/Asset/MC 3C.png |
Size of Cable N/A 1/0-1/0-1/0+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1028 |
Overall Diameter of Cable Over Armour (mils) N/A 1301 |
AL Weight (lb/mft) N/A 503 |
Cable Weight (lb/mft) N/A 629 |
A1/0-03MC3 A1/0-03MC3/Asset/MC 3C.png |
Size of Cable N/A 1/0-1/0-1/0+3 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3 |
Diameter of Ground (mils) N/A 238 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1047 |
Overall Diameter of Cable Over Armour (mils) N/A 1321 |
AL Weight (lb/mft) N/A 516 |
Cable Weight (lb/mft) N/A 644 |
A1/0-03MC2 A1/0-03MC2/Asset/MC 3C.png |
Size of Cable N/A 1/0-1/0-1/0+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1063 |
Overall Diameter of Cable Over Armour (mils) N/A 1337 |
AL Weight (lb/mft) N/A 531 |
Cable Weight (lb/mft) N/A 662 |
A1/0-03MC1 A1/0-03MC1/Asset/MC 3C.png |
Size of Cable N/A 1/0-1/0-1/0+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1079 |
Overall Diameter of Cable Over Armour (mils) N/A 1352 |
AL Weight (lb/mft) N/A 549 |
Cable Weight (lb/mft) N/A 689 |
A1/0-03MC1/0 A1/0-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 1/0-1/0-1/0+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1079 |
Overall Diameter of Cable Over Armour (mils) N/A 1352 |
AL Weight (lb/mft) N/A 569 |
Cable Weight (lb/mft) N/A 712 |
A2/0-03MC4 A2/0-03MC4/Asset/MC 3C.png |
Size of Cable N/A 2/0-2/0-2/0+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1118 |
Overall Diameter of Cable Over Armour (mils) N/A 1392 |
AL Weight (lb/mft) N/A 592 |
Cable Weight (lb/mft) N/A 730 |
A2/0-03MC2 A2/0-03MC2/Asset/MC 3C.png |
Size of Cable N/A 2/0-2/0-2/0+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1142 |
Overall Diameter of Cable Over Armour (mils) N/A 1415 |
AL Weight (lb/mft) N/A 618 |
Cable Weight (lb/mft) N/A 760 |
A2/0-03MC1 A2/0-03MC1/Asset/MC 3C.png |
Size of Cable N/A 2/0-2/0-2/0+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1157 |
Overall Diameter of Cable Over Armour (mils) N/A 1431 |
AL Weight (lb/mft) N/A 637 |
Cable Weight (lb/mft) N/A 787 |
A2/0-03MC1/0 A2/0-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 2/0-2/0-2/0+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1177 |
Overall Diameter of Cable Over Armour (mils) N/A 1451 |
AL Weight (lb/mft) N/A 660 |
Cable Weight (lb/mft) N/A 814 |
A2/0-03MC2/0 A2/0-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 2/0-2/0-2/0+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 2/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1177 |
Overall Diameter of Cable Over Armour (mils) N/A 1451 |
AL Weight (lb/mft) N/A 685 |
Cable Weight (lb/mft) N/A 842 |
A3/0-03MC4 A3/0-03MC4/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+4 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1197 |
Overall Diameter of Cable Over Armour (mils) N/A 1470 |
AL Weight (lb/mft) N/A 700 |
Cable Weight (lb/mft) N/A 850 |
A3/0-03MC2 A3/0-03MC2/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1220 |
Overall Diameter of Cable Over Armour (mils) N/A 1494 |
AL Weight (lb/mft) N/A 726 |
Cable Weight (lb/mft) N/A 880 |
A3/0-03MC1 A3/0-03MC1/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1248 |
Overall Diameter of Cable Over Armour (mils) N/A 1522 |
AL Weight (lb/mft) N/A 747 |
Cable Weight (lb/mft) N/A 909 |
A3/0-03MC1/0 A3/0-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1264 |
Overall Diameter of Cable Over Armour (mils) N/A 1537 |
AL Weight (lb/mft) N/A 769 |
Cable Weight (lb/mft) N/A 935 |
A3/0-03MC2/0 A3/0-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1283 |
Overall Diameter of Cable Over Armour (mils) N/A 1557 |
AL Weight (lb/mft) N/A 798 |
Cable Weight (lb/mft) N/A 967 |
A3/0-03MC3/0 A3/0-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 3/0-3/0-3/0+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 3/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1283 |
Overall Diameter of Cable Over Armour (mils) N/A 1557 |
AL Weight (lb/mft) N/A 830 |
Cable Weight (lb/mft) N/A 1003 |
A4/0-03MC2 A4/0-03MC2/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1346 |
Overall Diameter of Cable Over Armour (mils) N/A 1620 |
AL Weight (lb/mft) N/A 866 |
Cable Weight (lb/mft) N/A 1035 |
A4/0-03MC1 A4/0-03MC1/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1346 |
Overall Diameter of Cable Over Armour (mils) N/A 1620 |
AL Weight (lb/mft) N/A 882 |
Cable Weight (lb/mft) N/A 1060 |
A4/0-03MC1/0 A4/0-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1378 |
Overall Diameter of Cable Over Armour (mils) N/A 1652 |
AL Weight (lb/mft) N/A 907 |
Cable Weight (lb/mft) N/A 1088 |
A4/0-03MC2/0 A4/0-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1394 |
Overall Diameter of Cable Over Armour (mils) N/A 1667 |
AL Weight (lb/mft) N/A 935 |
Cable Weight (lb/mft) N/A 1119 |
A4/0-03MC3/0 A4/0-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1417 |
Overall Diameter of Cable Over Armour (mils) N/A 1691 |
AL Weight (lb/mft) N/A 970 |
Cable Weight (lb/mft) N/A 1159 |
A4/0-03MC4/0 A4/0-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 4/0-4/0-4/0+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 4/2000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1417 |
Overall Diameter of Cable Over Armour (mils) N/A 1691 |
AL Weight (lb/mft) N/A 1010 |
Cable Weight (lb/mft) N/A 1204 |
A250-03MC2 A250-03MC2/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1461 |
Overall Diameter of Cable Over Armour (mils) N/A 1734 |
AL Weight (lb/mft) N/A 993 |
Cable Weight (lb/mft) N/A 1203 |
A250-03MC1 A250-03MC1/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1496 |
Overall Diameter of Cable Over Armour (mils) N/A 1820 |
AL Weight (lb/mft) N/A 1065 |
Cable Weight (lb/mft) N/A 1284 |
A250-03MC1/0 A250-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1496 |
Overall Diameter of Cable Over Armour (mils) N/A 1820 |
AL Weight (lb/mft) N/A 1086 |
Cable Weight (lb/mft) N/A 1308 |
A250-03MC2/0 A250-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1528 |
Overall Diameter of Cable Over Armour (mils) N/A 1851 |
AL Weight (lb/mft) N/A 1116 |
Cable Weight (lb/mft) N/A 1342 |
A250-03MC3/0 A250-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1547 |
Overall Diameter of Cable Over Armour (mils) N/A 1871 |
AL Weight (lb/mft) N/A 1152 |
Cable Weight (lb/mft) N/A 1382 |
A250-03MC4/0 A250-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1575 |
Overall Diameter of Cable Over Armour (mils) N/A 1898 |
AL Weight (lb/mft) N/A 1197 |
Cable Weight (lb/mft) N/A 1432 |
A250-03MC250 A250-03MC250/Asset/MC 3C.png |
Size of Cable N/A 250-250-250+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1575 |
Overall Diameter of Cable Over Armour (mils) N/A 1898 |
AL Weight (lb/mft) N/A 1234 |
Cable Weight (lb/mft) N/A 1482 |
A300-03MC2 A300-03MC2/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1579 |
Overall Diameter of Cable Over Armour (mils) N/A 1902 |
AL Weight (lb/mft) N/A 1201 |
Cable Weight (lb/mft) N/A 1428 |
A300-03MC1 A300-03MC1/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1579 |
Overall Diameter of Cable Over Armour (mils) N/A 1902 |
AL Weight (lb/mft) N/A 1217 |
Cable Weight (lb/mft) N/A 1452 |
A300-03MC1/0 A300-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1614 |
Overall Diameter of Cable Over Armour (mils) N/A 1938 |
AL Weight (lb/mft) N/A 1244 |
Cable Weight (lb/mft) N/A 1483 |
A300-03MC2/0 A300-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1614 |
Overall Diameter of Cable Over Armour (mils) N/A 1938 |
AL Weight (lb/mft) N/A 1269 |
Cable Weight (lb/mft) N/A 1511 |
A300-03MC3/0 A300-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1650 |
Overall Diameter of Cable Over Armour (mils) N/A 1973 |
AL Weight (lb/mft) N/A 1308 |
Cable Weight (lb/mft) N/A 1554 |
A300-03MC4/0 A300-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1669 |
Overall Diameter of Cable Over Armour (mils) N/A 1993 |
AL Weight (lb/mft) N/A 1351 |
Cable Weight (lb/mft) N/A 1602 |
A300-03MC250 A300-03MC250/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1697 |
Overall Diameter of Cable Over Armour (mils) N/A 2020 |
AL Weight (lb/mft) N/A 1393 |
Cable Weight (lb/mft) N/A 1657 |
A300-03MC300 A300-03MC300/Asset/MC 3C.png |
Size of Cable N/A 300-300-300+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1697 |
Overall Diameter of Cable Over Armour (mils) N/A 2020 |
AL Weight (lb/mft) N/A 1438 |
Cable Weight (lb/mft) N/A 1708 |
A350-03MC2 A350-03MC2/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+2 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1638 |
Overall Diameter of Cable Over Armour (mils) N/A 1961 |
AL Weight (lb/mft) N/A 1348 |
Cable Weight (lb/mft) N/A 1589 |
A350-03MC1 A350-03MC1/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1673 |
Overall Diameter of Cable Over Armour (mils) N/A 1997 |
AL Weight (lb/mft) N/A 1371 |
Cable Weight (lb/mft) N/A 1620 |
A350-03MC1/0 A350-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1673 |
Overall Diameter of Cable Over Armour (mils) N/A 1997 |
AL Weight (lb/mft) N/A 1391 |
Cable Weight (lb/mft) N/A 1643 |
A350-03MC2/0 A350-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1713 |
Overall Diameter of Cable Over Armour (mils) N/A 2036 |
AL Weight (lb/mft) N/A 1424 |
Cable Weight (lb/mft) N/A 1680 |
A350-03MC3/0 A350-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1748 |
Overall Diameter of Cable Over Armour (mils) N/A 2072 |
AL Weight (lb/mft) N/A 1462 |
Cable Weight (lb/mft) N/A 1722 |
A350-03MC4/0 A350-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1748 |
Overall Diameter of Cable Over Armour (mils) N/A 2072 |
AL Weight (lb/mft) N/A 1502 |
Cable Weight (lb/mft) N/A 1767 |
A350-03MC250 A350-03MC250/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1772 |
Overall Diameter of Cable Over Armour (mils) N/A 2095 |
AL Weight (lb/mft) N/A 1543 |
Cable Weight (lb/mft) N/A 1821 |
A350-03MC300 A350-03MC300/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1799 |
Overall Diameter of Cable Over Armour (mils) N/A 2123 |
AL Weight (lb/mft) N/A 1593 |
Cable Weight (lb/mft) N/A 1877 |
A350-03MC350 A350-03MC350/Asset/MC 3C.png |
Size of Cable N/A 350-350-350+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1799 |
Overall Diameter of Cable Over Armour (mils) N/A 2123 |
AL Weight (lb/mft) N/A 1639 |
Cable Weight (lb/mft) N/A 1927 |
A400-03MC1 A400-03MC1/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1772 |
Overall Diameter of Cable Over Armour (mils) N/A 2095 |
AL Weight (lb/mft) N/A 1531 |
Cable Weight (lb/mft) N/A 1794 |
A400-03MC1/0 A400-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1772 |
Overall Diameter of Cable Over Armour (mils) N/A 2095 |
AL Weight (lb/mft) N/A 1551 |
Cable Weight (lb/mft) N/A 1817 |
A400-03MC2/0 A400-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1811 |
Overall Diameter of Cable Over Armour (mils) N/A 2135 |
AL Weight (lb/mft) N/A 1584 |
Cable Weight (lb/mft) N/A 1854 |
A400-03MC3/0 A400-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1811 |
Overall Diameter of Cable Over Armour (mils) N/A 2135 |
AL Weight (lb/mft) N/A 1616 |
Cable Weight (lb/mft) N/A 1890 |
A400-03MC4/0 A400-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1850 |
Overall Diameter of Cable Over Armour (mils) N/A 2174 |
AL Weight (lb/mft) N/A 1663 |
Cable Weight (lb/mft) N/A 1942 |
A400-03MC250 A400-03MC250/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1874 |
Overall Diameter of Cable Over Armour (mils) N/A 2198 |
AL Weight (lb/mft) N/A 1704 |
Cable Weight (lb/mft) N/A 1996 |
A400-03MC300 A400-03MC300/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1874 |
Overall Diameter of Cable Over Armour (mils) N/A 2198 |
AL Weight (lb/mft) N/A 1749 |
Cable Weight (lb/mft) N/A 2047 |
A400-03MC350 A400-03MC350/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1800 |
Cable Weight (lb/mft) N/A 2103 |
A400-03MC400 A400-03MC400/Asset/MC 3C.png |
Size of Cable N/A 400-400-400+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1848 |
Cable Weight (lb/mft) N/A 2154 |
A450-03MC1 A450-03MC1/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1827 |
Overall Diameter of Cable Over Armour (mils) N/A 2150 |
AL Weight (lb/mft) N/A 1677 |
Cable Weight (lb/mft) N/A 1954 |
A450-03MC1/0 A450-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1870 |
Overall Diameter of Cable Over Armour (mils) N/A 2194 |
AL Weight (lb/mft) N/A 1706 |
Cable Weight (lb/mft) N/A 1986 |
A450-03MC2/0 A450-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1870 |
Overall Diameter of Cable Over Armour (mils) N/A 2194 |
AL Weight (lb/mft) N/A 1731 |
Cable Weight (lb/mft) N/A 2014 |
A450-03MC3/0 A450-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1913 |
Overall Diameter of Cable Over Armour (mils) N/A 2237 |
AL Weight (lb/mft) N/A 1771 |
Cable Weight (lb/mft) N/A 2059 |
A450-03MC4/0 A450-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1953 |
Overall Diameter of Cable Over Armour (mils) N/A 2276 |
AL Weight (lb/mft) N/A 1818 |
Cable Weight (lb/mft) N/A 2111 |
A450-03MC250 A450-03MC250/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1953 |
Overall Diameter of Cable Over Armour (mils) N/A 2276 |
AL Weight (lb/mft) N/A 1855 |
Cable Weight (lb/mft) N/A 2161 |
A450-03MC300 A450-03MC300/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1976 |
Overall Diameter of Cable Over Armour (mils) N/A 2300 |
AL Weight (lb/mft) N/A 1904 |
Cable Weight (lb/mft) N/A 2216 |
A450-03MC350 A450-03MC350/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1976 |
Overall Diameter of Cable Over Armour (mils) N/A 2300 |
AL Weight (lb/mft) N/A 1950 |
Cable Weight (lb/mft) N/A 2266 |
A450-03MC400 A450-03MC400/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2012 |
Overall Diameter of Cable Over Armour (mils) N/A 2335 |
AL Weight (lb/mft) N/A 2004 |
Cable Weight (lb/mft) N/A 2324 |
A450-03MC450 A450-03MC450/Asset/MC 3C.png |
Size of Cable N/A 450-450-450+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2012 |
Overall Diameter of Cable Over Armour (mils) N/A 2335 |
AL Weight (lb/mft) N/A 2049 |
Cable Weight (lb/mft) N/A 2374 |
A500-03MC1 A500-03MC1/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1828 |
Cable Weight (lb/mft) N/A 2116 |
A500-03MC1/0 A500-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1949 |
Overall Diameter of Cable Over Armour (mils) N/A 2272 |
AL Weight (lb/mft) N/A 1857 |
Cable Weight (lb/mft) N/A 2148 |
A500-03MC2/0 A500-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1949 |
Overall Diameter of Cable Over Armour (mils) N/A 2272 |
AL Weight (lb/mft) N/A 1882 |
Cable Weight (lb/mft) N/A 2177 |
A500-03MC3/0 A500-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1992 |
Overall Diameter of Cable Over Armour (mils) N/A 2316 |
AL Weight (lb/mft) N/A 1922 |
Cable Weight (lb/mft) N/A 2221 |
A500-03MC4/0 A500-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1992 |
Overall Diameter of Cable Over Armour (mils) N/A 2316 |
AL Weight (lb/mft) N/A 1962 |
Cable Weight (lb/mft) N/A 2266 |
A500-03MC250 A500-03MC250/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2035 |
Overall Diameter of Cable Over Armour (mils) N/A 2359 |
AL Weight (lb/mft) N/A 2006 |
Cable Weight (lb/mft) N/A 2324 |
A500-03MC300 A500-03MC300/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2063 |
Overall Diameter of Cable Over Armour (mils) N/A 2387 |
AL Weight (lb/mft) N/A 2057 |
Cable Weight (lb/mft) N/A 2380 |
A500-03MC350 A500-03MC350/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2063 |
Overall Diameter of Cable Over Armour (mils) N/A 2387 |
AL Weight (lb/mft) N/A 2102 |
Cable Weight (lb/mft) N/A 2430 |
A500-03MC400 A500-03MC400/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2155 |
Cable Weight (lb/mft) N/A 2487 |
A500-03MC450 A500-03MC450/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2201 |
Cable Weight (lb/mft) N/A 2537 |
A500-03MC500 A500-03MC500/Asset/MC 3C.png |
Size of Cable N/A 500-500-500+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2246 |
Cable Weight (lb/mft) N/A 2586 |
A600-03MC1 A600-03MC1/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2106 |
Overall Diameter of Cable Over Armour (mils) N/A 2430 |
AL Weight (lb/mft) N/A 2144 |
Cable Weight (lb/mft) N/A 2524 |
A600-03MC1/0 A600-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2106 |
Overall Diameter of Cable Over Armour (mils) N/A 2430 |
AL Weight (lb/mft) N/A 2164 |
Cable Weight (lb/mft) N/A 2547 |
A600-03MC2/0 A600-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2146 |
Overall Diameter of Cable Over Armour (mils) N/A 2469 |
AL Weight (lb/mft) N/A 2197 |
Cable Weight (lb/mft) N/A 2583 |
A600-03MC3/0 A600-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2193 |
Overall Diameter of Cable Over Armour (mils) N/A 2517 |
AL Weight (lb/mft) N/A 2238 |
Cable Weight (lb/mft) N/A 2629 |
A600-03MC4/0 A600-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2287 |
Cable Weight (lb/mft) N/A 2683 |
A600-03MC250 A600-03MC250/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2323 |
Cable Weight (lb/mft) N/A 2733 |
A600-03MC300 A600-03MC300/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2291 |
Overall Diameter of Cable Over Armour (mils) N/A 2615 |
AL Weight (lb/mft) N/A 2378 |
Cable Weight (lb/mft) N/A 2793 |
A600-03MC350 A600-03MC350/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2291 |
Overall Diameter of Cable Over Armour (mils) N/A 2615 |
AL Weight (lb/mft) N/A 2423 |
Cable Weight (lb/mft) N/A 2842 |
A600-03MC400 A600-03MC400/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2476 |
Cable Weight (lb/mft) N/A 2900 |
A600-03MC450 A600-03MC450/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2521 |
Cable Weight (lb/mft) N/A 2950 |
A600-03MC500 A600-03MC500/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2567 |
Cable Weight (lb/mft) N/A 2999 |
A600-03MC600 A600-03MC600/Asset/MC 3C.png |
Size of Cable N/A 600-600-600+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2666 |
Cable Weight (lb/mft) N/A 3129 |
A650-03MC1 A650-03MC1/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2165 |
Overall Diameter of Cable Over Armour (mils) N/A 2489 |
AL Weight (lb/mft) N/A 2291 |
Cable Weight (lb/mft) N/A 2682 |
A650-03MC1/0 A650-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2165 |
Overall Diameter of Cable Over Armour (mils) N/A 2489 |
AL Weight (lb/mft) N/A 2311 |
Cable Weight (lb/mft) N/A 2705 |
A650-03MC2/0 A650-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2209 |
Overall Diameter of Cable Over Armour (mils) N/A 2532 |
AL Weight (lb/mft) N/A 2345 |
Cable Weight (lb/mft) N/A 2742 |
A650-03MC3/0 A650-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2256 |
Overall Diameter of Cable Over Armour (mils) N/A 2580 |
AL Weight (lb/mft) N/A 2386 |
Cable Weight (lb/mft) N/A 2787 |
A650-03MC4/0 A650-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2256 |
Overall Diameter of Cable Over Armour (mils) N/A 2580 |
AL Weight (lb/mft) N/A 2425 |
Cable Weight (lb/mft) N/A 2832 |
A650-03MC250 A650-03MC250/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2471 |
Cable Weight (lb/mft) N/A 2892 |
A650-03MC300 A650-03MC300/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2517 |
Cable Weight (lb/mft) N/A 2942 |
A650-03MC350 A650-03MC350/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2572 |
Cable Weight (lb/mft) N/A 3002 |
A650-03MC400 A650-03MC400/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2619 |
Cable Weight (lb/mft) N/A 3054 |
A650-03MC450 A650-03MC450/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2386 |
Overall Diameter of Cable Over Armour (mils) N/A 2709 |
AL Weight (lb/mft) N/A 2669 |
Cable Weight (lb/mft) N/A 3109 |
A650-03MC500 A650-03MC500/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2386 |
Overall Diameter of Cable Over Armour (mils) N/A 2709 |
AL Weight (lb/mft) N/A 2715 |
Cable Weight (lb/mft) N/A 3158 |
A650-03MC600 A650-03MC600/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2429 |
Overall Diameter of Cable Over Armour (mils) N/A 2753 |
AL Weight (lb/mft) N/A 2816 |
Cable Weight (lb/mft) N/A 3289 |
A650-03MC650 A650-03MC650/Asset/MC 3C.png |
Size of Cable N/A 650-650-650+650 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 650 |
Diameter of Ground (mils) N/A 843 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2429 |
Overall Diameter of Cable Over Armour (mils) N/A 2753 |
AL Weight (lb/mft) N/A 2861 |
Cable Weight (lb/mft) N/A 3338 |
A700-03MC1 A700-03MC1/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+1 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2448 |
Cable Weight (lb/mft) N/A 2852 |
A700-03MC1/0 A700-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2468 |
Cable Weight (lb/mft) N/A 2875 |
A700-03MC2/0 A700-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2493 |
Cable Weight (lb/mft) N/A 2904 |
A700-03MC3/0 A700-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2335 |
Overall Diameter of Cable Over Armour (mils) N/A 2658 |
AL Weight (lb/mft) N/A 2542 |
Cable Weight (lb/mft) N/A 2957 |
A700-03MC4/0 A700-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2335 |
Overall Diameter of Cable Over Armour (mils) N/A 2658 |
AL Weight (lb/mft) N/A 2582 |
Cable Weight (lb/mft) N/A 3002 |
A700-03MC250 A700-03MC250/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2390 |
Overall Diameter of Cable Over Armour (mils) N/A 2713 |
AL Weight (lb/mft) N/A 2628 |
Cable Weight (lb/mft) N/A 3063 |
A700-03MC300 A700-03MC300/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2390 |
Overall Diameter of Cable Over Armour (mils) N/A 2713 |
AL Weight (lb/mft) N/A 2674 |
Cable Weight (lb/mft) N/A 3113 |
A700-03MC350 A700-03MC350/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2441 |
Overall Diameter of Cable Over Armour (mils) N/A 2765 |
AL Weight (lb/mft) N/A 2729 |
Cable Weight (lb/mft) N/A 3173 |
A700-03MC400 A700-03MC400/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2441 |
Overall Diameter of Cable Over Armour (mils) N/A 2765 |
AL Weight (lb/mft) N/A 2776 |
Cable Weight (lb/mft) N/A 3225 |
A700-03MC450 A700-03MC450/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2472 |
Overall Diameter of Cable Over Armour (mils) N/A 2796 |
AL Weight (lb/mft) N/A 2827 |
Cable Weight (lb/mft) N/A 3280 |
A700-03MC500 A700-03MC500/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2472 |
Overall Diameter of Cable Over Armour (mils) N/A 2796 |
AL Weight (lb/mft) N/A 2873 |
Cable Weight (lb/mft) N/A 3329 |
A700-03MC600 A700-03MC600/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2973 |
Cable Weight (lb/mft) N/A 3460 |
A700-03MC700 A700-03MC700/Asset/MC 3C.png |
Size of Cable N/A 700-700-700+700 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 3065 |
Cable Weight (lb/mft) N/A 3560 |
A750-03MC1/0 A750-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2616 |
Cable Weight (lb/mft) N/A 3036 |
A750-03MC2/0 A750-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2641 |
Cable Weight (lb/mft) N/A 3064 |
A750-03MC3/0 A750-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2350 |
Overall Diameter of Cable Over Armour (mils) N/A 2674 |
AL Weight (lb/mft) N/A 2681 |
Cable Weight (lb/mft) N/A 3108 |
A750-03MC4/0 A750-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2406 |
Overall Diameter of Cable Over Armour (mils) N/A 2729 |
AL Weight (lb/mft) N/A 2731 |
Cable Weight (lb/mft) N/A 3164 |
A750-03MC250 A750-03MC250/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2777 |
Cable Weight (lb/mft) N/A 3224 |
A750-03MC300 A750-03MC300/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2822 |
Cable Weight (lb/mft) N/A 3274 |
A750-03MC350 A750-03MC350/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2868 |
Cable Weight (lb/mft) N/A 3324 |
A750-03MC400 A750-03MC400/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2925 |
Cable Weight (lb/mft) N/A 3386 |
A750-03MC450 A750-03MC450/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2971 |
Cable Weight (lb/mft) N/A 3436 |
A750-03MC500 A750-03MC500/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2543 |
Overall Diameter of Cable Over Armour (mils) N/A 2867 |
AL Weight (lb/mft) N/A 3022 |
Cable Weight (lb/mft) N/A 3491 |
A750-03MC600 A750-03MC600/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3123 |
Cable Weight (lb/mft) N/A 3622 |
A750-03MC700 A750-03MC700/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+700 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3215 |
Cable Weight (lb/mft) N/A 3723 |
A750-03MC750 A750-03MC750/Asset/MC 3C.png |
Size of Cable N/A 750-750-750+750 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3261 |
Cable Weight (lb/mft) N/A 3772 |
A800-03MC1/0 A800-03MC1/0/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+1/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2370 |
Overall Diameter of Cable Over Armour (mils) N/A 2694 |
AL Weight (lb/mft) N/A 2764 |
Cable Weight (lb/mft) N/A 3194 |
A800-03MC2/0 A800-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2370 |
Overall Diameter of Cable Over Armour (mils) N/A 2694 |
AL Weight (lb/mft) N/A 2789 |
Cable Weight (lb/mft) N/A 3223 |
A800-03MC3/0 A800-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2413 |
Overall Diameter of Cable Over Armour (mils) N/A 2737 |
AL Weight (lb/mft) N/A 2829 |
Cable Weight (lb/mft) N/A 3267 |
A800-03MC4/0 A800-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2469 |
Overall Diameter of Cable Over Armour (mils) N/A 2792 |
AL Weight (lb/mft) N/A 2879 |
Cable Weight (lb/mft) N/A 3323 |
A800-03MC250 A800-03MC250/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2469 |
Overall Diameter of Cable Over Armour (mils) N/A 2792 |
AL Weight (lb/mft) N/A 2916 |
Cable Weight (lb/mft) N/A 3372 |
A800-03MC300 A800-03MC300/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2524 |
Overall Diameter of Cable Over Armour (mils) N/A 2847 |
AL Weight (lb/mft) N/A 2971 |
Cable Weight (lb/mft) N/A 3434 |
A800-03MC350 A800-03MC350/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2524 |
Overall Diameter of Cable Over Armour (mils) N/A 2847 |
AL Weight (lb/mft) N/A 3017 |
Cable Weight (lb/mft) N/A 3483 |
A800-03MC400 A800-03MC400/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3074 |
Cable Weight (lb/mft) N/A 3546 |
A800-03MC450 A800-03MC450/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3120 |
Cable Weight (lb/mft) N/A 3595 |
A800-03MC500 A800-03MC500/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3165 |
Cable Weight (lb/mft) N/A 3644 |
A800-03MC600 A800-03MC600/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2610 |
Overall Diameter of Cable Over Armour (mils) N/A 2934 |
AL Weight (lb/mft) N/A 3264 |
Cable Weight (lb/mft) N/A 3773 |
A800-03MC700 A800-03MC700/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+700 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3364 |
Cable Weight (lb/mft) N/A 3882 |
A800-03MC750 A800-03MC750/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+750 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3410 |
Cable Weight (lb/mft) N/A 3931 |
A800-03MC800 A800-03MC800/Asset/MC 3C.png |
Size of Cable N/A 800-800-800+800 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 800 |
Diameter of Ground (mils) N/A 937 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3455 |
Cable Weight (lb/mft) N/A 3980 |
A900-03MC2/0 A900-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2504 |
Overall Diameter of Cable Over Armour (mils) N/A 2828 |
AL Weight (lb/mft) N/A 3092 |
Cable Weight (lb/mft) N/A 3550 |
A900-03MC3/0 A900-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2504 |
Overall Diameter of Cable Over Armour (mils) N/A 2828 |
AL Weight (lb/mft) N/A 3124 |
Cable Weight (lb/mft) N/A 3586 |
A900-03MC4/0 A900-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2610 |
Overall Diameter of Cable Over Armour (mils) N/A 2934 |
AL Weight (lb/mft) N/A 3184 |
Cable Weight (lb/mft) N/A 3652 |
A900-03MC250 A900-03MC250/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2610 |
Overall Diameter of Cable Over Armour (mils) N/A 2934 |
AL Weight (lb/mft) N/A 3220 |
Cable Weight (lb/mft) N/A 3701 |
A900-03MC300 A900-03MC300/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2669 |
Overall Diameter of Cable Over Armour (mils) N/A 2993 |
AL Weight (lb/mft) N/A 3276 |
Cable Weight (lb/mft) N/A 3763 |
A900-03MC350 A900-03MC350/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2669 |
Overall Diameter of Cable Over Armour (mils) N/A 2993 |
AL Weight (lb/mft) N/A 3322 |
Cable Weight (lb/mft) N/A 3813 |
A900-03MC400 A900-03MC400/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2669 |
Overall Diameter of Cable Over Armour (mils) N/A 2993 |
AL Weight (lb/mft) N/A 3369 |
Cable Weight (lb/mft) N/A 3865 |
A900-03MC450 A900-03MC450/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2724 |
Overall Diameter of Cable Over Armour (mils) N/A 3048 |
AL Weight (lb/mft) N/A 3425 |
Cable Weight (lb/mft) N/A 3925 |
A900-03MC500 A900-03MC500/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2724 |
Overall Diameter of Cable Over Armour (mils) N/A 3048 |
AL Weight (lb/mft) N/A 3470 |
Cable Weight (lb/mft) N/A 3974 |
A900-03MC600 A900-03MC600/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2760 |
Overall Diameter of Cable Over Armour (mils) N/A 3083 |
AL Weight (lb/mft) N/A 3569 |
Cable Weight (lb/mft) N/A 4104 |
A900-03MC700 A900-03MC700/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+700 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2760 |
Overall Diameter of Cable Over Armour (mils) N/A 3083 |
AL Weight (lb/mft) N/A 3662 |
Cable Weight (lb/mft) N/A 4204 |
A900-03MC750 A900-03MC750/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+750 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2807 |
Overall Diameter of Cable Over Armour (mils) N/A 3131 |
AL Weight (lb/mft) N/A 3716 |
Cable Weight (lb/mft) N/A 4263 |
A900-03MC800 A900-03MC800/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+800 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 800 |
Diameter of Ground (mils) N/A 937 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2807 |
Overall Diameter of Cable Over Armour (mils) N/A 3131 |
AL Weight (lb/mft) N/A 3762 |
Cable Weight (lb/mft) N/A 4312 |
A900-03MC900 A900-03MC900/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+900 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 900 |
Diameter of Ground (mils) N/A 1000 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2807 |
Overall Diameter of Cable Over Armour (mils) N/A 3131 |
AL Weight (lb/mft) N/A 3854 |
Cable Weight (lb/mft) N/A 4412 |
A900-03MC1000 A900-03MC1000/Asset/MC 3C.png |
Size of Cable N/A 900-900-900+1000 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 900 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1000 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1000 |
Diameter of Ground (mils) N/A 1059 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2807 |
Overall Diameter of Cable Over Armour (mils) N/A 3131 |
AL Weight (lb/mft) N/A 3947 |
Cable Weight (lb/mft) N/A 4512 |
A1000-03MC2/0 A1000-03MC2/0/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+2/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2634 |
Overall Diameter of Cable Over Armour (mils) N/A 2957 |
AL Weight (lb/mft) N/A 3394 |
Cable Weight (lb/mft) N/A 3875 |
A1000-03MC3/0 A1000-03MC3/0/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+3/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2634 |
Overall Diameter of Cable Over Armour (mils) N/A 2957 |
AL Weight (lb/mft) N/A 3426 |
Cable Weight (lb/mft) N/A 3911 |
A1000-03MC4/0 A1000-03MC4/0/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+4/0 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2681 |
Overall Diameter of Cable Over Armour (mils) N/A 3005 |
AL Weight (lb/mft) N/A 3475 |
Cable Weight (lb/mft) N/A 3965 |
A1000-03MC250 A1000-03MC250/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+250 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2744 |
Overall Diameter of Cable Over Armour (mils) N/A 3068 |
AL Weight (lb/mft) N/A 3523 |
Cable Weight (lb/mft) N/A 4027 |
A1000-03MC300 A1000-03MC300/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+300 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2744 |
Overall Diameter of Cable Over Armour (mils) N/A 3068 |
AL Weight (lb/mft) N/A 3568 |
Cable Weight (lb/mft) N/A 4078 |
A1000-03MC350 A1000-03MC350/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+350 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2803 |
Overall Diameter of Cable Over Armour (mils) N/A 3127 |
AL Weight (lb/mft) N/A 3625 |
Cable Weight (lb/mft) N/A 4139 |
A1000-03MC400 A1000-03MC400/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+400 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2803 |
Overall Diameter of Cable Over Armour (mils) N/A 3127 |
AL Weight (lb/mft) N/A 3672 |
Cable Weight (lb/mft) N/A 4191 |
A1000-03MC450 A1000-03MC450/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+450 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2803 |
Overall Diameter of Cable Over Armour (mils) N/A 3127 |
AL Weight (lb/mft) N/A 3717 |
Cable Weight (lb/mft) N/A 4240 |
A1000-03MC500 A1000-03MC500/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+500 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2866 |
Overall Diameter of Cable Over Armour (mils) N/A 3190 |
AL Weight (lb/mft) N/A 3775 |
Cable Weight (lb/mft) N/A 4302 |
A1000-03MC600 A1000-03MC600/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+600 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2902 |
Overall Diameter of Cable Over Armour (mils) N/A 3225 |
AL Weight (lb/mft) N/A 3874 |
Cable Weight (lb/mft) N/A 4431 |
A1000-03MC650 A1000-03MC650/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+650 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 650 |
Diameter of Ground (mils) N/A 843 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2902 |
Overall Diameter of Cable Over Armour (mils) N/A 3225 |
AL Weight (lb/mft) N/A 3919 |
Cable Weight (lb/mft) N/A 4480 |
A1000-03MC700 A1000-03MC700/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+700 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2902 |
Overall Diameter of Cable Over Armour (mils) N/A 3225 |
AL Weight (lb/mft) N/A 3966 |
Cable Weight (lb/mft) N/A 4532 |
A1000-03MC750 A1000-03MC750/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+750 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2902 |
Overall Diameter of Cable Over Armour (mils) N/A 3225 |
AL Weight (lb/mft) N/A 4012 |
Cable Weight (lb/mft) N/A 4581 |
A1000-03MC800 A1000-03MC800/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+800 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 800 |
Diameter of Ground (mils) N/A 937 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2902 |
Overall Diameter of Cable Over Armour (mils) N/A 3225 |
AL Weight (lb/mft) N/A 4057 |
Cable Weight (lb/mft) N/A 4630 |
A1000-03MC900 A1000-03MC900/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+900 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 900 |
Diameter of Ground (mils) N/A 1000 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2949 |
Overall Diameter of Cable Over Armour (mils) N/A 3272 |
AL Weight (lb/mft) N/A 4159 |
Cable Weight (lb/mft) N/A 4739 |
A1000-03MC1000 A1000-03MC1000/Asset/MC 3C.png |
Size of Cable N/A 1000-1000-1000+1000 |
Phase Conductor Size 7mÊÓƵ/MCM N/A 1000 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 1059 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor 7mÊÓƵ/MCM N/A 1000 |
Diameter of Ground (mils) N/A 1059 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2949 |
Overall Diameter of Cable Over Armour (mils) N/A 3272 |
AL Weight (lb/mft) N/A 4251 |
Cable Weight (lb/mft) N/A 4839 |