Single Conductor 600V Secondary Type URD Cable Aluminum Conductor
Single Conductor Type URD Cable - Aluminum Conductor
Applications
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.
Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications.
90ºC conductor temperature, 20ºC ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.
Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications.
- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
- B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
- B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
- Secondary UD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- "USE-2" per UL 854 available upon request.
- Cable in Duct (CIC)
- Abrasion Resistant
90ºC conductor temperature, 20ºC ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Size
|
Stranding |
Insulation
|
Outside
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|
Princeton Princeton/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 6 |
Stranding N/A 7/W |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .298 Inches |
Weight (lb/1000 ft) N/A 45 Lbs |
Ampacity Direct Burial N/A 90 Amps |
Ampacity In Duct N/A 65 Amps |
Mercer Mercer/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 4 |
Stranding N/A 7/W |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .345 Inches |
Weight (lb/1000 ft) N/A 64 Lbs |
Ampacity Direct Burial N/A 120 Amps |
Ampacity In Duct N/A 85 Amps |
Clemson Clemson/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 2 |
Stranding N/A 7/W |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .403 Inches |
Weight (lb/1000 ft) N/A 93 Lbs |
Ampacity Direct Burial N/A 155 Amps |
Ampacity In Duct N/A 115 Amps |
Kenyon Kenyon/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 1 |
Stranding N/A 19/W |
Insulation Thickness (mils) N/A 80 mls |
Outside Diameter N/A .522 Inches |
Weight (lb/1000 ft) N/A 148 Lbs |
Ampacity Direct Burial N/A 200 Amps |
Ampacity In Duct N/A 150 Amps |
Harvard Harvard/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 1/0 |
Stranding N/A 19/W |
Insulation Thickness (mils) N/A 80 mls |
Outside Diameter N/A .482 Inches |
Weight (lb/1000 ft) N/A 122 Lbs |
Ampacity Direct Burial N/A 175 Amps |
Ampacity In Duct N/A 130 Amps |
Yale Yale/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 2/0 |
Stranding N/A 19/W |
Insulation Thickness (mils) N/A 80 mls |
Outside Diameter N/A .566 Inches |
Weight (lb/1000 ft) N/A 179 Lbs |
Ampacity Direct Burial N/A 225 Amps |
Ampacity In Duct N/A 170 Amps |
Tufts Tufts/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 3/0 |
Stranding N/A 19/W |
Insulation Thickness (mils) N/A 80 mls |
Outside Diameter N/A .616 Inches |
Weight (lb/1000 ft) N/A 217 Lbs |
Ampacity Direct Burial N/A 250 Amps |
Ampacity In Duct N/A 195 Amps |
Beloit Beloit/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 4/0 |
Stranding N/A 19/W |
Insulation Thickness (mils) N/A 80 mls |
Outside Diameter N/A .672 Inches |
Weight (lb/1000 ft) N/A 265 Lbs |
Ampacity Direct Burial N/A 290 Amps |
Ampacity In Duct N/A 225 Amps |
Hofstra Hofstra/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 250 |
Stranding N/A 37/W |
Insulation Thickness (mils) N/A 95 mls |
Outside Diameter N/A .748 Inches |
Weight (lb/1000 ft) N/A 317 Lbs |
Ampacity Direct Burial N/A 320 Amps |
Ampacity In Duct N/A 250 Amps |
Gonzaga Gonzaga/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 300 |
Stranding N/A 37/W |
Insulation Thickness (mils) N/A 95 mls |
Outside Diameter N/A .801 Inches |
Weight (lb/1000 ft) N/A 371 Lbs |
Ampacity Direct Burial N/A 355 Amps |
Ampacity In Duct N/A 280 Amps |
Rutgers Rutgers/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 350 |
Stranding N/A 37/W |
Insulation Thickness (mils) N/A 95 mls |
Outside Diameter N/A .851 Inches |
Weight (lb/1000 ft) N/A 423 Lbs |
Ampacity Direct Burial N/A 385 Amps |
Ampacity In Duct N/A 305 Amps |
Emory Emory/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 500 |
Stranding N/A 37/W |
Insulation Thickness (mils) N/A 95 mls |
Outside Diameter N/A .979 Inches |
Weight (lb/1000 ft) N/A 579 Lbs |
Ampacity Direct Burial N/A 465 Amps |
Ampacity In Duct N/A 370 Amps |
Duke Duke/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 600 |
Stranding N/A 61/W |
Insulation Thickness (mils) N/A 110 mls |
Outside Diameter N/A 1.086 Inches |
Weight (lb/1000 ft) N/A 701 Lbs |
Ampacity Direct Burial N/A 510 Amps |
Ampacity In Duct N/A 410 Amps |
Furman Furman/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 700 |
Stranding N/A 61/W |
Insulation Thickness (mils) N/A 110 mls |
Outside Diameter N/A 1.155 Inches |
Weight (lb/1000 ft) N/A 804 Lbs |
Ampacity Direct Burial N/A 550 Amps |
Ampacity In Duct N/A 440 Amps |
Sewanee Sewanee/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 750 |
Stranding N/A 61/W |
Insulation Thickness (mils) N/A 110 mls |
Outside Diameter N/A 1.188 Inches |
Weight (lb/1000 ft) N/A 855 Lbs |
Ampacity Direct Burial N/A 580 Amps |
Ampacity In Duct N/A 470 Amps |
Fordham Fordham/Asset/SINGLE-URD.jpg |
Size (7mÊÓƵ or kcmil) N/A 1000 |
Stranding N/A 61/W |
Insulation Thickness (mils) N/A 110 mls |
Outside Diameter N/A 1.337 Inches |
Weight (lb/1000 ft) N/A 1109 Lbs |
Ampacity Direct Burial N/A 670 Amps |
Ampacity In Duct N/A 545 Amps |