10 7mÊÓƵ THWN or THHN PVC Jacket, 600V, 2/C - 37/C
TFN, THWN, or THHN - PVC Jacket, 600V
Applications
As flame-retardant multi-conductor control, signal or power cables rated 600 volts, 90 Deg. C. in dry locations, 75 Deg. C. in wet locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class 1 remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.
Construction
Individual conductors of stranded uncoated copper Type TFN (167mÊÓƵ). Type THWN or THHN (14-10 7mÊÓƵ), color coded, two conductors flat, three or more conductors twisted, PVC jacket overall, surface printed.
Standards
As flame-retardant multi-conductor control, signal or power cables rated 600 volts, 90 Deg. C. in dry locations, 75 Deg. C. in wet locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class 1 remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.
Construction
Individual conductors of stranded uncoated copper Type TFN (167mÊÓƵ). Type THWN or THHN (14-10 7mÊÓƵ), color coded, two conductors flat, three or more conductors twisted, PVC jacket overall, surface printed.
Standards
- Listed by UL as Type TC Tray Cable per Article 336 of the NEC.
- Individual conductors UL listed as Type THWN or THHN (14-10 7mÊÓƵ) or Type TFN (16 7mÊÓƵ).
- Overall jacket UL listed as Sunlight Resistant.
- Cables UL listed for Direct Burial.
- Cables with grounding conductor UL listed for Open Wiring.
- Cables pass UL and IEEE-383 ribbon burner tests and ICEA 210.00 BTU/hour test.
- Cables designated (w/g) contain an additional bare copper grounding conductor, same size as circuit conductors, and are UL listed for Open Wiring.
- Standard color coding is ICEA Method E2 or K2 for NEC applications. This color coding method omits white and green from the color sequence.
- ICEA Method 4 color coding is also provided. This consists of printed numbers and words, 1-ONE, 2-TWO, etc.
- Size 16 7mÊÓƵ is rated 90ºC dry only.
Item # |
Number
|
Size
|
Number
|
Overall
|
Nominal
|
Weight
|
---|---|---|---|---|---|---|
10-TC1-2 10-TC1-2/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 2 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 45 |
Nominal Diameter (in) N/A .26 x .43 |
Weight (lb/1000 ft) N/A 110 Lbs |
10-TC1-3 10-TC1-3/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 3 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 45 |
Nominal Diameter (in) N/A 0.46 |
Weight (lb/1000 ft) N/A 155 Lbs |
10-TC1-3 w/g 10-TC1-3 w/g/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 3 w/g |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 45 |
Nominal Diameter (in) N/A 0.47 |
Weight (lb/1000 ft) N/A 194 Lbs |
10-TC1-4 10-TC1-4/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 4 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 45 |
Nominal Diameter (in) N/A 0.50 |
Weight (lb/1000 ft) N/A 200 Lbs |
10-TC1-5 10-TC1-5/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 5 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.58 |
Weight (lb/1000 ft) N/A 265 Lbs |
10-TC1-6 10-TC1-6/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 6 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.63 |
Weight (lb/1000 ft) N/A 315 Lbs |
10-TC1-7 10-TC1-7/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 7 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.63 |
Weight (lb/1000 ft) N/A 345 Lbs |
10-TC1-8 10-TC1-8/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 8 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.69 |
Weight (lb/1000 ft) N/A 420 Lbs |
10-TC1-9 10-TC1-9/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 9 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.73 |
Weight (lb/1000 ft) N/A 450 Lbs |
10-TC1-10 10-TC1-10/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 10 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.81 |
Weight (lb/1000 ft) N/A 500 Lbs |
10-TC1-11 10-TC1-11/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 11 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.81 |
Weight (lb/1000 ft) N/A 540 Lbs |
10-TC1-12 10-TC1-12/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 12 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.82 |
Weight (lb/1000 ft) N/A 580 Lbs |
10-TC1-13 10-TC1-13/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 13 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 0.89 |
Weight (lb/1000 ft) N/A 680 Lbs |
10-TC1-14 10-TC1-14/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 14 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 0.92 |
Weight (lb/1000 ft) N/A 725 Lbs |
10-TC1-15 10-TC1-15/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 15 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 0.95 |
Weight (lb/1000 ft) N/A 745 Lbs |
10-TC1-16 10-TC1-16/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 16 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 0.95 |
Weight (lb/1000 ft) N/A 810 Lbs |
10-TC1-17 10-TC1-17/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 17 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.02 |
Weight (lb/1000 ft) N/A 860 Lbs |
10-TC1-18 10-TC1-18/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 18 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.02 |
Weight (lb/1000 ft) N/A 900 Lbs |
10-TC1-19 10-TC1-19/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 19 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.02 |
Weight (lb/1000 ft) N/A 940 Lbs |
10-TC1-20 10-TC1-20/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 20 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.07 |
Weight (lb/1000 ft) N/A 990 Lbs |
10-TC1-23 10-TC1-23/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 23 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.12 |
Weight (lb/1000 ft) N/A 1120 Lbs |
10-TC1-25 10-TC1-25/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 25 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.19 |
Weight (lb/1000 ft) N/A 1210 Lbs |
10-TC1-27 10-TC1-27/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 27 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.22 |
Weight (lb/1000 ft) N/A 1295 Lbs |
10-TC1-29 10-TC1-29/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 29 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.23 |
Weight (lb/1000 ft) N/A 1375 Lbs |
10-TC1-31 10-TC1-31/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 31 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.29 |
Weight (lb/1000 ft) N/A 1465 Lbs |
10-TC1-32 10-TC1-32/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 32 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.31 |
Weight (lb/1000 ft) N/A 1510 Lbs |
10-TC1-37 10-TC1-37/Asset/VNTC-PVC-Jacket-600V.png |
Number of Conductors N/A 37 |
Size (7mÊÓƵ or kcmil) N/A 10 |
Number of Strands N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.36 |
Weight (lb/1000 ft) N/A 1710 Lbs |