8 7mÊÓƵ - 1000 MCM, THWN or THHN PVC Jacket, 600V, 3/C with Ground
THWN or THHN - PVC Jacket, 600V with Ground
Applications
As flame-retardant three-conductor power cables rated 600 volts, 90 Deg. C. in dry locations. 75 Deg. C. in wet locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Individual conductors of stranded uncoated copper Type THWN or THHN, surface print phase identification. Three insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and fillers, cable tape, PVC jacket overall, surface printed.
Standards
As flame-retardant three-conductor power cables rated 600 volts, 90 Deg. C. in dry locations. 75 Deg. C. in wet locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Individual conductors of stranded uncoated copper Type THWN or THHN, surface print phase identification. Three insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and fillers, cable tape, PVC jacket overall, surface printed.
Standards
- Listed by UL as Type TC Tray Cable per Article 336 of the NEC.
- Individual conductors UL listed as Type THWN or THHN.
- Overall jacket UL listed as Sunlight Resistant.
- Cables UL listed for Direct Burial.
- Cables UL listed for Open Wiring.
- Cables pass UL and IEEE-383 ribbon burner tests and ICEA 210.00 BTU/hour test.
- AMPACITY in accordance with the National Electric Code for cables in uncovered cable tray without maintained space and for cable in raceway or direct buried. 90 ºC conductor temperature for dry locations, 75 ºC conductor temperature for wet locations, 30 ºC ambient temperature.
- Grounding conductor per UL Standard 1277 for Type TC Tray Cable.
Item # |
Number
|
Size
|
Number
|
PVC Insulation
|
Nylon
|
Overall
|
Nominal
|
Grounding
|
Weight
|
---|---|---|---|---|---|---|---|---|---|
TC3-8 TC3-8/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 8 |
Number of Strands N/A 7 |
PVC Insulation Thickness (mils) N/A 30 |
Nylon Jacket Thickness (Mils) N/A 5 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.62 |
Grounding Conductor Size 7mÊÓƵ N/A 10 |
Weight (lb/1000 ft) N/A 315 Lbs |
TC3-6 TC3-6/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 6 |
Number of Strands N/A 7 |
PVC Insulation Thickness (mils) N/A 30 |
Nylon Jacket Thickness (Mils) N/A 5 |
Overall PVC Jacket (mils) N/A 60 |
Nominal Diameter (in) N/A 0.70 |
Grounding Conductor Size 7mÊÓƵ N/A 8 |
Weight (lb/1000 ft) N/A 445 Lbs |
TC3-4 TC3-4/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 4 |
Number of Strands N/A 7 |
PVC Insulation Thickness (mils) N/A 40 |
Nylon Jacket Thickness (Mils) N/A 6 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 0.88 |
Grounding Conductor Size 7mÊÓƵ N/A 8 |
Weight (lb/1000 ft) N/A 675 Lbs |
TC3-2 TC3-2/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 2 |
Number of Strands N/A 7 |
PVC Insulation Thickness (mils) N/A 40 |
Nylon Jacket Thickness (Mils) N/A 6 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.01 |
Grounding Conductor Size 7mÊÓƵ N/A 6 |
Weight (lb/1000 ft) N/A 995 Lbs |
TC3-1 TC3-1/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 1 |
Number of Strands N/A 19 |
PVC Insulation Thickness (mils) N/A 50 |
Nylon Jacket Thickness (Mils) N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.14 |
Grounding Conductor Size 7mÊÓƵ N/A 6 |
Weight (lb/1000 ft) N/A 1200 Lbs |
TC3-1/0 TC3-1/0/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 1/0 |
Number of Strands N/A 19 |
PVC Insulation Thickness (mils) N/A 50 |
Nylon Jacket Thickness (Mils) N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.23 |
Grounding Conductor Size 7mÊÓƵ N/A 6 |
Weight (lb/1000 ft) N/A 1480 Lbs |
TC3-2/0 TC3-2/0/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 2/0 |
Number of Strands N/A 19 |
PVC Insulation Thickness (mils) N/A 50 |
Nylon Jacket Thickness (Mils) N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.32 |
Grounding Conductor Size 7mÊÓƵ N/A 6 |
Weight (lb/1000 ft) N/A 1770 Lbs |
TC3-3/0 TC3-3/0/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 3/0 |
Number of Strands N/A 19 |
PVC Insulation Thickness (mils) N/A 50 |
Nylon Jacket Thickness (Mils) N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.42 |
Grounding Conductor Size 7mÊÓƵ N/A 4 |
Weight (lb/1000 ft) N/A 2180 Lbs |
TC3-4/0 TC3-4/0/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 4/0 |
Number of Strands N/A 19 |
PVC Insulation Thickness (mils) N/A 50 |
Nylon Jacket Thickness (Mils) N/A 7 |
Overall PVC Jacket (mils) N/A 80 |
Nominal Diameter (in) N/A 1.56 |
Grounding Conductor Size 7mÊÓƵ N/A 4 |
Weight (lb/1000 ft) N/A 2690 Lbs |
TC3-250 TC3-250/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 250 |
Number of Strands N/A 37 |
PVC Insulation Thickness (mils) N/A 60 |
Nylon Jacket Thickness (Mils) N/A 8 |
Overall PVC Jacket (mils) N/A 110 |
Nominal Diameter (in) N/A 1.76 |
Grounding Conductor Size 7mÊÓƵ N/A 4 |
Weight (lb/1000 ft) N/A 3225 Lbs |
TC3-350 TC3-350/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 350 |
Number of Strands N/A 37 |
PVC Insulation Thickness (mils) N/A 60 |
Nylon Jacket Thickness (Mils) N/A 8 |
Overall PVC Jacket (mils) N/A 110 |
Nominal Diameter (in) N/A 1.98 |
Grounding Conductor Size 7mÊÓƵ N/A 3 |
Weight (lb/1000 ft) N/A 4370 Lbs |
TC3-500 TC3-500/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 500 |
Number of Strands N/A 37 |
PVC Insulation Thickness (mils) N/A 60 |
Nylon Jacket Thickness (Mils) N/A 8 |
Overall PVC Jacket (mils) N/A 110 |
Nominal Diameter (in) N/A 2.26 |
Grounding Conductor Size 7mÊÓƵ N/A 2 |
Weight (lb/1000 ft) N/A 5960 Lbs |
TC3-750 TC3-750/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 750 |
Number of Strands N/A 61 |
PVC Insulation Thickness (mils) N/A 70 |
Nylon Jacket Thickness (Mils) N/A 9 |
Overall PVC Jacket (mils) N/A 110 |
Nominal Diameter (in) N/A 2.71 |
Grounding Conductor Size 7mÊÓƵ N/A 1 |
Weight (lb/1000 ft) N/A 9050 Lbs |
TC3-1000 TC3-1000/Asset/VNTC-PVC-Jacket-600V-wGROUND.png |
Number of Conductors N/A 3 |
Size 7mÊÓƵ or KCMIL N/A 1000 |
Number of Strands N/A 61 |
PVC Insulation Thickness (mils) N/A 70 |
Nylon Jacket Thickness (Mils) N/A 9 |
Overall PVC Jacket (mils) N/A 140 |
Nominal Diameter (in) N/A 3.10 |
Grounding Conductor Size 7mÊÓƵ N/A 1/0 |
Weight (lb/1000 ft) N/A 11720 Lbs |