Triplex Conductor 600V Secondary Type URD Cable - (8000) RHH/RHW-2 USE-2 - Aluminum Conductor
Triplex Conductor Type URD Cable - Aluminum Conductor
Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
Construction
Concentric stranded or compressed 8000 (8176-H24) aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
Construction
Concentric stranded or compressed 8000 (8176-H24) aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
- B-800 8000 Series Aluminum Alloy Wire for Electrical Purposes
- B-801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation.
- B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
- Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- UL Standard 44 for Type RHH or RHW-2
- UL standard 854 for Type USE-2.
- Cable in Duct (CIC)
- Abrasion Resistant
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Unit of Measure
Items |
/Asset/TRIPLEX-URD.jpg Erskine Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor |
/Asset/TRIPLEX-URD.jpg Vassar Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor |
/Asset/TRIPLEX-URD.jpg Stephens Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor |
/Asset/TRIPLEX-URD.jpg Ramapo Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor |
/Asset/TRIPLEX-URD.jpg Brenau Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor |
|||||
Phase Conductor Size/7mÊÓƵ |
N/A 6 | N/A 4 | N/A 2 | N/A 2 | N/A 1/0 | |||||
Phase Conductor Stranding |
N/A 7/w | N/A 7/w | N/A 7/w | N/A 7/w | N/A 19/w | |||||
Phase Conductor Insulation Thickness |
N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 80 mls | |||||
Neutral Size 7mÊÓƵ | N/A 6 | N/A 4 | N/A 4 | N/A 2 | N/A 2 | |||||
Neutral Stranding | N/A 7/w | |||||||||
Neutral Insulation Thickness | N/A 60 mls | |||||||||
Single Phase Conductor |
N/A .299 Inches | N/A .345 Inches | N/A .403 Inches | N/A .403 Inches | N/A .522 Inches | |||||
Outside Diameter |
N/A .646 Inches | N/A .754 Inches | N/A .842 Inches | N/A .874 Inches | N/A 1.064 Inches | |||||
Weight (lb/1000 ft) |
N/A 143 Lbs | N/A 203 Lbs | N/A 264 Lbs | N/A 294 Lbs | N/A 408 Lbs | |||||
Ampacity Direct Burial |
N/A 95 Amps | N/A 125 Amps | N/A 165 Amps | N/A 165 Amps | N/A 215 Amps | |||||
Ampacity In Duct |
N/A 70 Amps | N/A 90 Amps | N/A 120 Amps | N/A 120 Amps | N/A 160 Amps | |||||
|