7m视频

Print Back
Applications
This cable is designed for high voltage connections between power distribution systems in mines, mine tunnels, shafts, and mine load centers where continuous monitoring of the ground system is required. This cable is suitable for installation in Ducts, troughs, tray or direct burial for non-flexing service.

Construction
  • Conductor is stranded annealed copper enveloped in a strand shield.
  • Insulation is Ethylene Propylene Rubber (EPR) or Cross Linked Polyethylene (XLPE).
  • Assembly is semi-conducting tape and a metallic tape shield with grounding conductors consisting of two bare grounds and one 8-gauge insulated ground check that are cabled together in the interstices of the power conductors and fillers are added to make round.
  • A single faced rubber filled tape is applied overlapped.
  • Jacket is Chlorinated Polyethylene (CPE).
Standards
Conforms to ICEA S-66-524 (NEMA WC8).

Notes
  • Shipping tolerance +/- 10%
Type MP-GC (Mine Power Feeder)
Unit of Measure
1 

Item #

Power
Conductors
Size 7m视频

Power
Conductors
# of Strands

Power
Conductors
Insulation
Thickness

Ground Wire
Size 7m视频

Ground Wire
# of Strands

Jacket
Thickness
(Inches)

Overall
Diameter
(inches)

Net Weight
Per MFT

MP8-01-4 N/A 4 N/A 7 N/A 0.115 Inches N/A 8 N/A 7 N/A 0.11 N/A 1.43 N/A 1440 Lbs
MP8-02-2 N/A 2 N/A 7 N/A 0.115 Inches N/A 6 N/A 7 N/A 0.11 N/A 1.55 N/A 1760 Lbs
MP8-03-1 N/A 1 N/A 19 N/A 0.115 Inches N/A 5 N/A 7 N/A 0.11 N/A 1.65 N/A 2070 Lbs
MP8-04-1/0 N/A 1/0 N/A 19 N/A 0.115 Inches N/A 4 N/A 7 N/A 0.11 N/A 1.75 N/A 2440 Lbs
MP8-05-2/0 N/A 2/0 N/A 19 N/A 0.115 Inches N/A 3 N/A 7 N/A 0.14 N/A 1.88 N/A 2940 Lbs
MP8-06-4/0 N/A 4/0 N/A 19 N/A 0.115 Inches N/A 1/0 N/A 19 N/A 0.14 N/A 2.12 N/A 4130 Lbs
MP8-07-250 N/A 250 N/A 37 N/A 0.115 Inches N/A 2/0 N/A 19 N/A 0.14 N/A 2.25 N/A 4760 Lbs
MP8-08-350 N/A 350 N/A 37 N/A 0.115 Inches N/A 3/0 N/A 19 N/A 0.14 N/A 2.46 N/A 6090 Lbs
MP8-09-500 N/A 500 N/A 37 N/A 0.115 Inches N/A 4/0 N/A 19 N/A 0.14 N/A 2.75 N/A 8360 Lbs
Unit of Measure
1