Application
PowerGuard®-XL cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. They are suitable for installation in duct or direct burial.
Construction
Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength PowerGuard®-XL TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethylene jacket.
Description
Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231, or compact strand per AST B400. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Extruded, Tree Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing both electrical integrity and ease of stripping.
Metallic Shield: Solid flat strap copper wires helically applied and uniformly spaced.
Crushing of round wires to make flat wires shall not be allowed. Water-blocking agents applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
Water Block: Water-blocking agents applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirements are 15 psig for 1 hour.
Jacket: Black insulating sunlight resistant linear low-density polyethylene encapsulating the neutral wires with three extruded red stripes and NESC lightning bolt symbol.
Standards
• ASTM B-231 or B400
• AEIC CS8
• ICEA S-94-649
• ICEA T-31-610
• ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
• UL 1072 MV-105
Insulation Temperature Rating |
|
Normal |
105º C |
Emergency* |
140ºC |
Short Circuit |
250º C |
*Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable.
Physical Properties of Extruded-to-Fill XLPE Jacket |
|
Unaged Tensile Strength, min. (PSI) |
1500 |
Aged* Tensile Strength, min. ret. (%) |
70 |
Unaged Elongated, min. (%) |
150 |
Aged* Elongated, min. ret. (%) |
70 |
Heat Distortion 1 hr at 131 ºC, max. (%) |
3 |
*Aged for 168 hrs at 121 ºC
Options
• Copper Conductors
Item # |
Conductor
|
Nominal
|
Approx.
|
Minimum
|
Maximum
|
Nominal
|
Neutral
|
Number
|
Flat
|
Approx.
|
Nominal
|
Approx.
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
A1/0S-01UD35GT101XFS A1/0S-01UD35GT101XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1/0 SOLID |
Nominal Conductor Diameter (inches) N/A 0.325 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 97 |
Minimum Insulation O.D. (inches) N/A 1.010 |
Maximum Insulation O.D. (inches) N/A 1.110 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A Full |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 148 |
Nominal Jacket O.D. (inches) N/A 1.271 |
Approx. Total Weight (LBs/KFT) N/A 721 |
A1/0S-01UD35GT203XFS A1/0S-01UD35GT203XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1/0 SOLID |
Nominal Conductor Diameter (inches) N/A 0.325 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 97 |
Minimum Insulation O.D. (inches) N/A 1.010 |
Maximum Insulation O.D. (inches) N/A 1.110 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 2/3 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 99 |
Nominal Jacket O.D. (inches) N/A 1.271 |
Approx. Total Weight (LBs/KFT) N/A 675 |
A1/0-01UD35GT101XFS A1/0-01UD35GT101XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1/0 |
Nominal Conductor Diameter (inches) N/A 0.336 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 99 |
Minimum Insulation O.D. (inches) N/A 1.020 |
Maximum Insulation O.D. (inches) N/A 1.120 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A Full |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 148 |
Nominal Jacket O.D. (inches) N/A 1.282 |
Approx. Total Weight (LBs/KFT) N/A 737 |
A1/0-01UD35GT203XFS A1/0-01UD35GT203XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1/0 |
Nominal Conductor Diameter (inches) N/A 0.336 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 99 |
Minimum Insulation O.D. (inches) N/A 1.020 |
Maximum Insulation O.D. (inches) N/A 1.120 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 2/3 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 99 |
Nominal Jacket O.D. (inches) N/A 1.282 |
Approx. Total Weight (LBs/KFT) N/A 691 |
A3/0-01UD35GT101XFS A3/0-01UD35GT101XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 3/0 |
Nominal Conductor Diameter (inches) N/A 0.423 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 158 |
Minimum Insulation O.D. (inches) N/A 1.105 |
Maximum Insulation O.D. (inches) N/A 1.205 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A Full |
Number Of Straps N/A 15 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 247 |
Nominal Jacket O.D. (inches) N/A 1.369 |
Approx. Total Weight (LBs/KFT) N/A 944 |
A3/0-01UD35GT203XFS A3/0-01UD35GT203XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 3/0 |
Nominal Conductor Diameter (inches) N/A 0.423 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 158 |
Minimum Insulation O.D. (inches) N/A 1.105 |
Maximum Insulation O.D. (inches) N/A 1.205 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 2/3 |
Number Of Straps N/A 10 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 165 |
Nominal Jacket O.D. (inches) N/A 1.369 |
Approx. Total Weight (LBs/KFT) N/A 868 |
A3/0-01UD35GT103XFS A3/0-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 3/0 |
Nominal Conductor Diameter (inches) N/A 0.423 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 158 |
Minimum Insulation O.D. (inches) N/A 1.105 |
Maximum Insulation O.D. (inches) N/A 1.205 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 99 |
Nominal Jacket O.D. (inches) N/A 1.369 |
Approx. Total Weight (LBs/KFT) N/A 808 |
A4/0-01UD35GT101XFS A4/0-01UD35GT101XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 4/0 |
Nominal Conductor Diameter (inches) N/A 0.475 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 199 |
Minimum Insulation O.D. (inches) N/A 1.160 |
Maximum Insulation O.D. (inches) N/A 1.260 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A Full |
Number Of Straps N/A 18 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 297 |
Nominal Jacket O.D. (inches) N/A 1.421 |
Approx. Total Weight (LBs/KFT) N/A 1,065 |
A4/0-01UD35GT203XFS A4/0-01UD35GT203XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 4/0 |
Nominal Conductor Diameter (inches) N/A 0.475 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 199 |
Minimum Insulation O.D. (inches) N/A 1.160 |
Maximum Insulation O.D. (inches) N/A 1.260 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 2/3 |
Number Of Straps N/A 12 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 198 |
Nominal Jacket O.D. (inches) N/A 1.421 |
Approx. Total Weight (LBs/KFT) N/A 974 |
A4/0-01UD35GT102XFS A4/0-01UD35GT102XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 4/0 |
Nominal Conductor Diameter (inches) N/A 0.475 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 199 |
Minimum Insulation O.D. (inches) N/A 1.160 |
Maximum Insulation O.D. (inches) N/A 1.260 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 1/2 |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 148 |
Nominal Jacket O.D. (inches) N/A 1.421 |
Approx. Total Weight (LBs/KFT) N/A 929 |
A4/0-01UD35GT103XFS A4/0-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 4/0 |
Nominal Conductor Diameter (inches) N/A 0.475 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 199 |
Minimum Insulation O.D. (inches) N/A 1.160 |
Maximum Insulation O.D. (inches) N/A 1.260 |
Nominal Jacket Thickness (inches) N/A 0.055 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 99 |
Nominal Jacket O.D. (inches) N/A 1.421 |
Approx. Total Weight (LBs/KFT) N/A 883 |
A350-01UD35GT102XFS A350-01UD35GT102XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 350 |
Nominal Conductor Diameter (inches) N/A 0.616 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 329 |
Minimum Insulation O.D. (inches) N/A 1.310 |
Maximum Insulation O.D. (inches) N/A 1.410 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/2 |
Number Of Straps N/A 15 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 247 |
Nominal Jacket O.D. (inches) N/A 1.570 |
Approx. Total Weight (LBs/KFT) N/A 1,254 |
A350-01UD35GT103XFS A350-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 350 |
Nominal Conductor Diameter (inches) N/A 0.616 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 329 |
Minimum Insulation O.D. (inches) N/A 1.310 |
Maximum Insulation O.D. (inches) N/A 1.410 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 10 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 165 |
Nominal Jacket O.D. (inches) N/A 1.570 |
Approx. Total Weight (LBs/KFT) N/A 1,179 |
A350-01UD35GT106XFS A350-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 350 |
Nominal Conductor Diameter (inches) N/A 0.616 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 329 |
Minimum Insulation O.D. (inches) N/A 1.310 |
Maximum Insulation O.D. (inches) N/A 1.410 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 99 |
Nominal Jacket O.D. (inches) N/A 1.570 |
Approx. Total Weight (LBs/KFT) N/A 1,118 |
A500-01UD35GT102XFS A500-01UD35GT102XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 500 |
Nominal Conductor Diameter (inches) N/A 0.736 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 468 |
Minimum Insulation O.D. (inches) N/A 1.430 |
Maximum Insulation O.D. (inches) N/A 1.530 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/2 |
Number Of Straps N/A 18 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 351 |
Nominal Jacket O.D. (inches) N/A 1.740 |
Approx. Total Weight (LBs/KFT) N/A 1,628 |
A500-01UD35GT103XFS A500-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 500 |
Nominal Conductor Diameter (inches) N/A 0.736 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 468 |
Minimum Insulation O.D. (inches) N/A 1.430 |
Maximum Insulation O.D. (inches) N/A 1.530 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 12 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 234 |
Nominal Jacket O.D. (inches) N/A 1.740 |
Approx. Total Weight (LBs/KFT) N/A 1,521 |
A500-01UD35GT106XFS A500-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 500 |
Nominal Conductor Diameter (inches) N/A 0.736 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 468 |
Minimum Insulation O.D. (inches) N/A 1.430 |
Maximum Insulation O.D. (inches) N/A 1.530 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 117 |
Nominal Jacket O.D. (inches) N/A 1.740 |
Approx. Total Weight (LBs/KFT) N/A 1,413 |
A750-01UD35GT103XFS A750-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 750 |
Nominal Conductor Diameter (inches) N/A 0.908 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 703 |
Minimum Insulation O.D. (inches) N/A 1.610 |
Maximum Insulation O.D. (inches) N/A 1.710 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 18 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 351 |
Nominal Jacket O.D. (inches) N/A 1.920 |
Approx. Total Weight (LBs/KFT) N/A 2,008 |
A750-01UD35GT106XFS A750-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 750 |
Nominal Conductor Diameter (inches) N/A 0.908 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 703 |
Minimum Insulation O.D. (inches) N/A 1.610 |
Maximum Insulation O.D. (inches) N/A 1.710 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 176 |
Nominal Jacket O.D. (inches) N/A 1.920 |
Approx. Total Weight (LBs/KFT) N/A 1,847 |
A1000-01UD35GT103XFS A1000-01UD35GT103XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1000 |
Nominal Conductor Diameter (inches) N/A 1.060 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 937 |
Minimum Insulation O.D. (inches) N/A 1.760 |
Maximum Insulation O.D. (inches) N/A 1.865 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/3 |
Number Of Straps N/A 24 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 468 |
Nominal Jacket O.D. (inches) N/A 2.072 |
Approx. Total Weight (LBs/KFT) N/A 2,468 |
A1000-01UD35GT106XFS A1000-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1000 |
Nominal Conductor Diameter (inches) N/A 1.060 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 937 |
Minimum Insulation O.D. (inches) N/A 1.760 |
Maximum Insulation O.D. (inches) N/A 1.865 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 12 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 234 |
Nominal Jacket O.D. (inches) N/A 2.072 |
Approx. Total Weight (LBs/KFT) N/A 2,254 |
A1000-01UD35GT108XFS A1000-01UD35GT108XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1000 |
Nominal Conductor Diameter (inches) N/A 1.060 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 937 |
Minimum Insulation O.D. (inches) N/A 1.760 |
Maximum Insulation O.D. (inches) N/A 1.865 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/8 (3) |
Number Of Straps N/A 10 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 195 |
Nominal Jacket O.D. (inches) N/A 2.072 |
Approx. Total Weight (LBs/KFT) N/A 2,218 |
A1000-01UD35GT112XFS A1000-01UD35GT112XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1000 |
Nominal Conductor Diameter (inches) N/A 1.060 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 937 |
Minimum Insulation O.D. (inches) N/A 1.760 |
Maximum Insulation O.D. (inches) N/A 1.865 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/12 |
Number Of Straps N/A 6 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 117 |
Nominal Jacket O.D. (inches) N/A 2.072 |
Approx. Total Weight (LBs/KFT) N/A 2,146 |
A1250-01UD35GT106XFS A1250-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1250 |
Nominal Conductor Diameter (inches) N/A 1.184 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1172 |
Minimum Insulation O.D. (inches) N/A 1.890 |
Maximum Insulation O.D. (inches) N/A 1.995 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 15 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 293 |
Nominal Jacket O.D. (inches) N/A 2.204 |
Approx. Total Weight (LBs/KFT) N/A 2,616 |
A1250-01UD35GT108XFS A1250-01UD35GT108XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1250 |
Nominal Conductor Diameter (inches) N/A 1.184 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1172 |
Minimum Insulation O.D. (inches) N/A 1.890 |
Maximum Insulation O.D. (inches) N/A 1.995 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/8 (3) |
Number Of Straps N/A 13 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 254 |
Nominal Jacket O.D. (inches) N/A 2.204 |
Approx. Total Weight (LBs/KFT) N/A 2,580 |
A1250-01UD35GT112XFS A1250-01UD35GT112XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1250 |
Nominal Conductor Diameter (inches) N/A 1.184 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1172 |
Minimum Insulation O.D. (inches) N/A 1.890 |
Maximum Insulation O.D. (inches) N/A 1.995 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/12 |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 163 |
Approx. Copper Weight (LBs/KFT) N/A 148 |
Nominal Jacket O.D. (inches) N/A 2.204 |
Approx. Total Weight (LBs/KFT) N/A 2,483 |
A1500-01UD35GT106XFS A1500-01UD35GT106XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1500 |
Nominal Conductor Diameter (inches) N/A 1.299 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1406 |
Minimum Insulation O.D. (inches) N/A 2.005 |
Maximum Insulation O.D. (inches) N/A 2.110 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/6 |
Number Of Straps N/A 18 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 351 |
Nominal Jacket O.D. (inches) N/A 2.319 |
Approx. Total Weight (LBs/KFT) N/A 3,032 |
A1500-01UD35GT108XFS A1500-01UD35GT108XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1500 |
Nominal Conductor Diameter (inches) N/A 1.299 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1406 |
Minimum Insulation O.D. (inches) N/A 2.005 |
Maximum Insulation O.D. (inches) N/A 2.110 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/8 (3) |
Number Of Straps N/A 15 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 293 |
Nominal Jacket O.D. (inches) N/A 2.319 |
Approx. Total Weight (LBs/KFT) N/A 2,978 |
A1500-01UD35GT112XFS A1500-01UD35GT112XFS/Asset/flat-strap.png |
Conductor Size 7mÊÓƵ or kcmil N/A 1500 |
Nominal Conductor Diameter (inches) N/A 1.299 |
Approx. Aluminum Conductor Weight (LBs/KFT) N/A 1406 |
Minimum Insulation O.D. (inches) N/A 2.005 |
Maximum Insulation O.D. (inches) N/A 2.110 |
Nominal Jacket Thickness (inches) N/A 0.080 |
Neutral Configuration N/A 1/12 |
Number Of Straps N/A 9 |
Flat Strap Dimensions (mils) N/A 25 X 193 |
Approx. Copper Weight (LBs/KFT) N/A 176 |
Nominal Jacket O.D. (inches) N/A 2.319 |
Approx. Total Weight (LBs/KFT) N/A 2,871 |