Quadruplex Service Drop Aluminum Conductors - AAC Neutral-Messenger
Quadruplex Service Drop Aluminum Conductor
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded AAC. One conductor is manufactured with an extruded ridge for phase identification.
Standards
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded AAC. One conductor is manufactured with an extruded ridge for phase identification.
Standards
- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Item # |
Phase
|
Phase
|
Phase
|
Bare
|
Bare
|
Bare
|
Weight
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|
Clydesdale Clydesdale/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4 |
Bare Neutral Messenger Stranding N/A 7 |
Bare Neutral Messenger Breaking Strength N/A 881 Lbs |
Weight Per (lb/1000 ft) XLP N/A 208 Lbs |
Weight (lb/1000 ft) Poly N/A 201.8 Lbs |
Ampacity XLP N/A 100 Amps |
Ampacity Poly N/A 80 Amps |
Pinto Pinto/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4 |
Bare Neutral Messenger Stranding N/A 7 |
Bare Neutral Messenger Breaking Strength N/A 881 Lbs |
Weight Per (lb/1000 ft) XLP N/A 223 Lbs |
Weight (lb/1000 ft) Poly N/A 207.9 Lbs |
Ampacity XLP N/A 100 Amps |
Ampacity Poly N/A 80 Amps |
Mustang Mustang/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 2 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 2 |
Bare Neutral Messenger Stranding N/A 7 |
Bare Neutral Messenger Breaking Strength N/A 1350 Lbs |
Weight Per (lb/1000 ft) XLP N/A 333 Lbs |
Weight (lb/1000 ft) Poly N/A 312.6 Lbs |
Ampacity XLP N/A 135 Amps |
Ampacity Poly N/A 105 Amps |
Criollo Criollo/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 1/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 1/0 |
Bare Neutral Messenger Stranding N/A 7 |
Bare Neutral Messenger Breaking Strength N/A 1990 Lbs |
Weight Per (lb/1000 ft) XLP N/A 529 Lbs |
Weight (lb/1000 ft) Poly N/A 504.5 Lbs |
Ampacity XLP N/A 180 Amps |
Ampacity Poly N/A 140 Amps |
Percheron Percheron/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 2/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 2/0 |
Bare Neutral Messenger Stranding N/A 7 |
Bare Neutral Messenger Breaking Strength N/A 2510 Lbs |
Weight Per (lb/1000 ft) XLP N/A 649 Lbs |
Weight (lb/1000 ft) Poly N/A 620.5 Lbs |
Ampacity XLP N/A 205 Amps |
Ampacity Poly N/A 160 Amps |
Hanoverian Hanoverian/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 3/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 3/0 |
Bare Neutral Messenger Stranding N/A 19 |
Bare Neutral Messenger Breaking Strength N/A 3310 Lbs |
Weight Per (lb/1000 ft) XLP N/A 799 Lbs |
Weight (lb/1000 ft) Poly N/A 765.6 Lbs |
Ampacity XLP N/A 235 Amps |
Ampacity Poly N/A 185 Amps |
Oldenburg Oldenburg/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4/0 |
Bare Neutral Messenger Stranding N/A 19 |
Bare Neutral Messenger Breaking Strength N/A 4020 Lbs |
Weight Per (lb/1000 ft) XLP N/A 986 Lbs |
Weight (lb/1000 ft) Poly N/A 946.7 Lbs |
Ampacity XLP N/A 275 Amps |
Ampacity Poly N/A 210 Amps |
Lippizaner Lippizaner/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 336.4 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 80 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 336.4 |
Bare Neutral Messenger Stranding N/A 19 |
Bare Neutral Messenger Breaking Strength N/A 6146 Lbs |
Weight Per (lb/1000 ft) XLP N/A 1546 Lbs |
Weight (lb/1000 ft) Poly N/A 1519.2 Lbs |
Ampacity XLP N/A 370 Amps |
Ampacity Poly N/A 280 Amps |