Quadruplex Service Drop Aluminum Conductor
quadruplex-service-drop-cable-aluminum-conductor
-
Quadruplex Service Drop Aluminum Conductors - AAC Neutral-Messenger
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded AAC. One conductor is manufactured with an extruded ridge for phase identification.
Standards- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition. -
Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition. -
Quadruplex Service Drop Aluminum Conductors AAAC 6201 Alloy Neutral-Messenger
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 潞C for polyethylene insulated conductors or 90 潞C for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201 alloy. One conductor is manufactured with an extruded ridge for phase identification.
Standards- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 潞C for XLR 75 潞C for Poly; ambient temperatures of 40 潞C emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition. -
PACKAGING INFORMATION: Quadruplex Service Drop Aluminum Conductor
Packaging Information: Quadruplex Service Drop Aluminum Conductor CODE
WORDALUMINUM
CONDUCTORSSTANDARD PACKAGE SIZES PHASE
SIZE AND STRANDINGNEUTRAL SIZE AND STRANDING LENGTH WEIGHT
PE
(lbs)WEIGHT
XLP
(lbs)REEL
SIZEAAC Neutral Messenger Pinto 4-7 4-7 500 106 109 Coil 1,500 317 327 NRC 36.24 Mustang 2-7 2-7 500 159 163 Coil 1,800 571 587 NRC 42.26 Libyan 1/0-7 1/0-7 550 281 288 NRC 36.24 1,100 561 576 NRC 42.26 Criollo 1/0-19 1/0-7 550 278 286 NRC 36.24 1,100 556 572 NRC 42.26 Orloff 2/0-7 2/0-7 750 472 485 NRC 36.24 1,500 944 969 NRC 50.32 Percheron 2/0-19 2/0-7 750 467 479 NRC 36.24 1,500 933 959 NRC 50.32 Mongolian 3/0-7 3/0-7 650 504 517 NRC 36.24 1,300 1009 1034 NRC 50.32 Hanoverian 3/0-19 3/0-19 650 499 512 NRC 36.24 1,300 998 1,023 NRC 50.32 Singlefoot 4/0-7 4/0-7 500 481 492 NRC 40.24 1,000 961 983 NRC 50.32 Oldenberg 4/0-19 4/0-19 500 475 486 NRC 40.24 1,000 950 971 NRC 50.32 Mongolian 3/0-7 3/0-7 650 504 517 NRC 36.24 1,300 1009 1034 NRC 50.32 Hanoverian 3/0-19 3/0-19 650 499 512 NRC 36.24 1,300 998 1,023 NRC 50.32 Singlefoot 4/0-7 4/0-7 500 481 492 NRC 40.24 1,000 961 983 NRC 50.32 Oldenberg 4/0-19 4/0-19 500 475 486 NRC 40.24 1,000 950 971 NRC 50.32 ACSR Messenger Chola 6-7 6-6/1 500 77 80 Coil 2,100 322 334 NRC 36.24 Hackney 4-7 4-6/1 500 115 118 Coil 1,500 344 354 NRC 36.24 Palornino 2-7 2-6/1 500 173 178 Coil 1,800 623 639 NRC 42.26 Standardbred 1/0-7 1/0-6/1 550 306 315 NRC 36.24 1,100 612 629 NRC 42.26 Costena 1/0-19 1/0-6/1 550 303 311 NRC 36.24 1,200 606 623 NRC 42.26 Chicoteagues 2/0-7 2/0-6/1 750 515 528 NRC 36.24 1,500 1031 1056 NRC 50.32 Grullo 2/0-19 2/0-6/1 750 510 523 NRC 36.24 1,500 1,020 1,046 NRC 50.32 Mare 3/0-7 3/0-6/1 650 522 565 NRC 36.24 1,300 1,104 1,130 NRC 50.32 Suffolk 3/0-19 3/0-6/1 650 547 559 NRC 36.24 1,300 1,093 1,118 NRC 50.32 Stallion 4/0-7 4/0-6/1 500 527 538 NRC 40.24 1,000 1,053 1,075 NRC 50.32 Appaloosa 4/0-19 4/0-16/1 500 521 532 NRC 40.24 1,000 1,042 1,063 NRC 50.32 Bronco 336.4-19 336.4-18/1 1,000 1510 1587 NRC 50.32 AAAC-6201 Alloy Neutral Messenger French Coach 6-7 6-7 500 73 76 Coil 2,000 290 302 NRC 36.24 Arabian 4-7 4-7 500 109 112 Coil 1,500 326 336 NRC 36.24 Belgian 2-7 2-7 500 164 169 Coil 1,800 589 607 NRC 42.26 Plow 1/0-7 1/0-7 550 290 298 NRC 36.24 1,100 580 596 NRC 42.26 Shetland 1/0-19 1/0-7 550 287 295 NRC 36.24 1,100 574 591 NRC 42.26 Dapple-Grey 2/0-7 2/0-7 750 488 500 NRC 36.24 1,500 975 1001 NRC 50.32 Thoroughbred 2/0-19 2/0-7 750 482 495 NRC 36.24 1,500 965 990 NRC 50.32 Dobbin 3/0-7 3/0-7 650 521 534 NRC 36.24 1,300 1,043 1,069 NRC 50.32 Trotter 3/0-19 3/0-7 650 516 528 NRC 36.24 1,300 1,032 1,057 NRC 50.32 Pony 4/0-7 4/0-7 500 497 508 NRC 40.24 1,000 994 1,016 NRC 50.32 Walking 4/0-19 4/0-7 500 492 502 NRC 40.24 1,000 983 1004 NRC 50.32