Quadruplex Service Drop Aluminum Conductors - ACSR Neutral-Messenger
Quadruplex Service Drop Aluminum Conductor
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors or 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards
- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90 ºC for XLR 75 ºC for Poly; ambient temperatures of 40 ºC emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Item # |
Phase
|
Phase
|
Phase
|
Bare
|
Bare
|
Bare
|
Weight
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|
Morochuca Morochuca/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 6 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 6 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 1190 Lbs |
Weight Per (lb/1000 ft) XLP N/A 152 Lbs |
Weight (lb/1000 ft) Poly N/A 147.4 Lbs |
Ampacity XLP N/A 75 Amps |
Ampacity Poly N/A 60 Amps |
Chola Chola/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 6 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 6 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 1190 Lbs |
Weight Per (lb/1000 ft) XLP N/A 162 Lbs |
Weight (lb/1000 ft) Poly N/A 151.7 Lbs |
Ampacity XLP N/A 75 Amps |
Ampacity Poly N/A 60 Amps |
Morgan Morgan/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 1860 Lbs |
Weight Per (lb/1000 ft) XLP N/A 226 Lbs |
Weight (lb/1000 ft) Poly N/A 220 Lbs |
Ampacity XLP N/A 100 Amps |
Ampacity Poly N/A 80 Amps |
Hackney Hackney/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 1860 Lbs |
Weight Per (lb/1000 ft) XLP N/A 241 Lbs |
Weight (lb/1000 ft) Poly N/A 226.1 Lbs |
Ampacity XLP N/A 100 Amps |
Ampacity Poly N/A 80 Amps |
Palomino Palomino/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 2 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness N/A 45 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 2 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 2850 Lbs |
Weight Per (lb/1000 ft) XLP N/A 362 Lbs |
Weight (lb/1000 ft) Poly N/A 342.6 Lbs |
Ampacity XLP N/A 135 Amps |
Ampacity Poly N/A 105 Amps |
Costena Costena/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 1/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 1/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 4380 Lbs |
Weight Per (lb/1000 ft) XLP N/A 575 Lbs |
Weight (lb/1000 ft) Poly N/A 550.6 Lbs |
Ampacity XLP N/A 180 Amps |
Ampacity Poly N/A 140 Amps |
Grullo Grullo/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 2/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 2/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 5310 Lbs |
Weight Per (lb/1000 ft) XLP N/A 707 Lbs |
Weight (lb/1000 ft) Poly N/A 678.7 Lbs |
Ampacity XLP N/A 205 Amps |
Ampacity Poly N/A 160 Amps |
Suffolk Suffolk/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 3/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 3/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 6620 Lbs |
Weight Per (lb/1000 ft) XLP N/A 872 Lbs |
Weight (lb/1000 ft) Poly N/A 838.9 Lbs |
Ampacity XLP N/A 235 Amps |
Ampacity Poly N/A 185 Amps |
Appaloosa Appaloosa/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 4/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 60 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 8350 Lbs |
Weight Per (lb/1000 ft) XLP N/A 1079 Lbs |
Weight (lb/1000 ft) Poly N/A 1039.2 Lbs |
Ampacity XLP N/A 275 Amps |
Ampacity Poly N/A 210 Amps |
Bronco Bronco/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 336.4 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 80 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 336.4 |
Bare Neutral Messenger Stranding N/A 18/1 |
Bare Neutral Messenger Breaking Strength N/A 8580 Lbs |
Weight Per (lb/1000 ft) XLP N/A 1613 Lbs |
Weight (lb/1000 ft) Poly N/A 1568.2 Lbs |
Ampacity XLP N/A 370 Amps |
Ampacity Poly N/A 280 Amps |
Gelding Gelding/Asset/QUAD-SERVICE-DROP.jpg |
Phase Conductor Size/7mÊÓƵ N/A 336.4 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness N/A 80 mls |
Bare Neutral Messenger Size/7mÊÓƵ N/A 4/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength N/A 8350 Lbs |
Weight Per (lb/1000 ft) XLP N/A 1548 Lbs |
Weight (lb/1000 ft) Poly N/A 1494.3 Lbs |
Ampacity XLP N/A 370 Amps |
Ampacity Poly N/A 280 Amps |